Technical Specifications InRow™ Chilled Water Air Conditioners Up to 70 kW
Schneider Electric IT Corporation Legal Disclaimer The information presented in this manual is not warranted by the Schneider Electric IT Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan.
Table of Contents Technical Data............................................................................................ 1 Model Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Model identification label location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Capacity . . . . .
Recommended Capacity Limitations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 ACRC301S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 ACRC301H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 ACRC500/ACRP500 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 ACRC301S . . . . . . . . . . .
With Cooling Distribution Unit (CDU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Without CDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 ACRC500/ACRP500 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 ACRC500/ACRP500 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data Model Identification Model identification label location 300 mm 600 mm NAMEPLATE Rear NAMEPLATE Model Width Range of Capacity ACRC301S 300 mm Up to 45 kW No 100–240V 1 50/60 Hz NEMA L5-20P/ IEC 309-16A ACRC301H 300 mm Up to 60 kW No 208–230V 1 50/60 Hz HARDWIRED ACRC500 600 mm Up to 70 kW No 200–240V 3 50/60 Hz HARDWIRED Optional: NEMA L21-20P ACRC501 600 mm Up to 70 kW No 460–480V 3 50/60 Hz HARDWIRED ACRC502 600 mm Up to 70 kW No 380–415V 3 50/
Overview The modular, row-based computer room cooling solutions offers efficient, predictable, and economical cooling for a variety of spaces. Critical environmental requirements now reach far beyond the confines of the traditional data center or computer room to encompass a larger suite of applications, referred to as technology rooms.
Scalable Solutions for Critical Environments Advantages of row-based cooling InRow cooling products improve energy efficiency and cooling ability in a number of ways. First, the InRow CW air conditioner draws air directly from the hot aisle, allowing the InRow unit to take advantage of higher heat transfer efficiency due to higher temperature differences. It can then discharge room-temperature air directly in front of the servers it is cooling.
EcoAisle™ Aisle Containment System Modular ceiling tiles and doors/curtains can be used to enclose the hot aisle. This increases the densities that can be handled in a single rack enclosure by eliminating mixing of hot and cold air streams. This method, called load neutralization, removes the heat from the hot aisle, cools it, and then returns it to the surrounding room area.
Hot aisle containment dimensions 1200 1200 1070 1200 900 1070 HOT AISLE 1200 1070 1070 900 900 900 Hot Aisle - Middle or End of Aisle, Frame to Frame, With Depth Extenders Nominal Aisle Width 914 (36.00) 991 (39.00) 991 (39.00) 991 (39.00) 1291 (50.83) 1291 (50.83) 1591 (50.83) -- 991 (39.00) 991 (39.00) 1161 (45.71) 1161 (45.71) 1461 (45.71) -- -- 991 (39.00) 1161 (45.71) 1161 (45.71) 1331 (52.40) -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 1296 (51.
Cold aisle containment dimensions 1200 1200 1070 1200 1070 900 COLD AISLE 1200 1070 900 900 900 1070 Nominal Aisle Width 991 (39) Cold Aisle - Middle of Aisle, Frame to Frame, With Depth Extenders 914 (36) 1121 (44.13) -- 1121 (44.13) -- 1121 (44.13) -- -- -- 991 (39.00) -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 1426 (56.14) 1296 (51.02) 1426 (56.14) 1296 (51.02) -1219 (48) 1296 (51.02) 1426 (56.14) 1296 (51.02) -- -- 1296 (51.
Configurations Chilled water systems utilize water from a chiller plant for cooling. Chilled water is commonly used in large buildings and high rises and can serve multiple indoor units, which can be cost effective for large installation options. There are various methods for chilled water piping.
Standard Features and Options Standard features Insulated side panels The frame is constructed of 16 gauge formed steel for maximum strength. Cabinet is serviceable from the front and rear. All exterior panels and corner posts on the frame are powder coated for durability and an attractive finish. Front and rear exterior panels are constructed of 18 gauge perforated steel with 84% open free area. Insulation is 80.1 kg/m3 (5 lb/ft3) density and complies with ASTM E84 rating of 25/50.
30% ASHRAE 52.1 filter (ACRC500/ACRP500 series only) The filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by electrical equipment. The system uses a 30% efficient, 102 mm (4 in), deep loading, pleated filter. Deeper filters produce a lower pressure drop, requiring less energy during normal operation. The filter is moisture resistant up to a 100% relative humidity. Filters are easily replaceable from the rear of the unit. (MERV 8 per ASHRAE 52.
Optional features Cable water detector A leak detection cable for 300-mm units (NBES0308 and NBES0309) or 600-mm units (AP9325 and AP9326) is placed on the floor or sub-floor around all possible leak sources. If water or other conductive liquids contact the cable anywhere along its length, the microprocessor controller visually and audibly announces a leak. The 6.1-m (20-ft) cable may be cascaded to make custom lengths up to 24.4 m (80 ft).
85% ASHRAE 52.1 filter (ACRC500/ACRP500 series only) 990-4618C-001 Electrical equipment requires clean, particle free air, thus making the filtration of the air extremely important. Optionally, the system uses an 85% efficient, 102-mm (4-in.), deep loading, pleated filter. Deeper filters produce a lower pressure drop, requiring less energy during normal operation. The 100% synthetic media will not absorb moisture and is resistant to most common chemicals.
Microprocessor Controller The microprocessor controller user interface allows the unit to be turned on or off and displays the configuration and condition of the unit. ACRC301S/ACRC301H Display Reset 10/100 USB Console 12 na4820a Micro SD Service Port Item Description Function LCD display 4.3-in. touch-screen color display. Power LED The cooling unit is powered when the LED is illuminated. Unit firmware is updating when LED is blinking.
ACRC500/ACRP500 &KHFN /RJ ? 0LQRU $ODUP 0DMRU $ODUP na0262a ESC 6WDWXV Item Function Major Alarm LED When lit, a major alarm condition exists. Minor Alarm LED When lit, a minor alarm condition exists. Check Log LED When lit, at least one new major alarm or minor alarm or event has occurred. Status LED When lit, the Module is on. Liquid Crystal Display (LCD) View alarms, status data, instructional help, and configuration items.
Control type The controller utilizes proportional/integral/derivative (PID) settings, a time-proven precision environmental control method. This allows for custom tuning of control variables to achieve optimal system response. Functions • Supply and Return Air Conditions • Operational Mode Control • Data Logging (ACRC301 series) • Event Logging • Alarms • Redundant Group Control • Fan Speed Adjustment • Input/Output Module Programming Logging The event log keeps a record of all alarms and events.
Alarms The microprocessor controller shall activate a visible and audible alarm in the following occurrences: • Active Flow Controller sensor fault • Air filter clogged • Air filter run hours violation • Check condensate management system • Chilled water flow meter fault • Chilled water valve actuator fault • Chilled water valve control not set to automatic • Coil chilled water temperature sensor error • Coil condensation possible • Condensate pan full (excluding ACRC301H) • Controller power supply X fault
ACRC500/ACRP500 series only • Fan run hours exceeded • Condensate run hours exceeded • Group communication fault • Invalid supply setpoint • Link isolation relay fault ACRP500 series only • Humidifier water conductivity high • Humidifier fault tolerance exceeded • Humidifier low water • Humidifier excessive output reduction • Humidifier drain fault • Humidifier cylinder full • Humidifier replace cylinder • Humidifier RS485 communication fault • Humidity high/low violation • Supply humidity sensor fault • R
InRow ACRC301S/ACRC301H Models na4303a External components - ACRC301S Item Description 990-4618C-001 Upper side panels Fans Display interface Lower side panels Front panel Rear panel Air filters Upper piping installation holes InRow Chilled Water Air Conditioners Technical Specifications 17
na4345a External components - ACRC301H Item Description 18 Upper side panels Fans Display interface Lower side panels Front panel Rear panel Air filters Upper piping installation holes InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
na4397a Internal components - ACRC301S Item Description Item Description Fan Inlet shutoff valve (1 in.
na4333a Internal components - ACRC301H Item 20 Description Item Description Fan Pipe connection, water outlet Supply air temperature sensor, top Return air temperature sensor, bottom Supply air temperature sensor, bottom 3-way valve actuator Coil Top pipe connection for optional recirculation pump Flow meter Humidity sensor Bottom pipe connection for optional recirculation pump Auto transfer switch (ATS) box Drain valve Electrical box Inlet s
na4335a User interface connection panel - ACRC301S Item 990-4618C-001 Description Upper electrical box cover User interface connection panel Control module cover InRow Chilled Water Air Conditioners Technical Specifications 21
na4433a User interface connection panel - ACRC301H Item 22 Description Upper electrical box cover User interface connection panel Control module cover InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
P510 P509 P511 P512 P508 P507 SW1 P513 P506 P505 P504 SW503 P503 SW502 SW501 P502 na4434a P501 P514 Interface connection Item Description Item Description Universal sensor ports USB host port Network connection Serial port Touchscreen display connection A-Link port ModBus connection Reset button ModBus configuration switches Output relay 4/standby input Processor status LED Output relay 1–3 USB device port 990-4618C-001 InRow Chilled
InRow ACRC500/ACRP500 Series External components Item 24 Description Item Description Removable rear doors Removable front door Side panel lock Top access for customer network wiring Removable side panel Top power connection Adjustable leveling foot Top humidifier supply (ACRP series only) Caster Top condensate drain Door handle and lock Top supply (inlet) Display interface Top return (outlet) InRow Chilled Water Air Conditioners Technical Specif
Internal mechanical components (front) DB FEE DA na2090a FEE Item Description Item Description Electric heater (ACRP500 series only) Electrical panel Fan Supply air temperature sensors Fan guard Main feed breakers Humidifier (ACRP500 series only) User interface connectors Condensate drain pan Ground wire Condensate pump Supply humidity sensor 990-4618C-001 InRow Chilled Water Air Conditioners Technical Specifications 25
Internal mechanical components (rear) Item 26 Description Item Description Chilled water coil Rear doors Chilled water control actuator and threeway valve Air filters Sensor Return humidity sensor (ACRP500 series only) Flow meter Return temperature sensor Pipe chase InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
User interface connection Item Description Item Description Rack inlet temperature sensors 1, 2, 3 A-Link IN A-Link OUT Supply 24 V DC (current limit: 20 mA) Customer input + (12–30 V AC/V DC, 24 V DC @ 11 mA) Customer input - (12–30 V AC/V DC, 24 V DC @ 11 mA) Network port Modbus D1 Console port Customer output, NC (Normally Closed) Customer output, COM (Common) Modbus D0 Modbus GND Supply air temperature sensor (front) Supply air humidity sensor (front
Electrical panel 28 Item Description Transformers User interface connectors Main controller board Relay board Ground lug Main circuit breaker — power feed A Main circuit breaker — power feed B Automatic transfer switch (ATS) contactors ATS timers ATS transformer (ACRP501/ACRC501 only) ATS circuit breakers Fan circuit breakers Controller circuit breaker Humidifier circuit breaker (ACRP500 series only) Heater circuit breaker (ACRP500 series only)
Determining Cooling Capacity IT equipment requires two acceptable limits in order for effective cooling to occur. These parameters are inlet air temperature and flow rate of air through the IT equipment. It is entirely possible, though undesirable, to design a computer room with enough heat removal capacity, but with an inadequate volumetric flow rate of cool air supply.
Recommended Capacity Limitations ACRC301S IT Equipment IT Equipment Air Flow Recommended Capacity Limit °C (°F) l/s per kW (CFM/kW) kW 5.56 (10) 8.33 (15) 11.11 (20) 13.89 (25) 16.67 (30) 19.44 (35) 22.22 (40) 25 (45) 150 (317) 100 (211) 75 (158) 60 (128) 50 (107) 43 (92) 38 (81) 34 (72) 10.1 15.1 20.3 25.0 30.0 34.7 39.7 44.7 IT Equipment Air Flow Recommended Capacity Limit °C (°F) l/s per kW (CFM/kW) kW 5.56 (10) 8.33 (15) 11.11 (20) 13.89 (25) 16.67 (30) 19.44 (35) 22.
ACRC301S Performance Specifications 5°C (41°F) EWT Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 21.3 (73000) 20.9 (71000) 0.98 0.97 (15.4) 49.8 (16.7) 6.6°C (12°F) 19.5 (67000) 19.1 (65000) 0.98 0.71 (11.3) 29.3 (9.8) 7.7°C (14°F) 18.0 (62000) 17.7 (60000) 0.98 0.59 (9.3) 20.5 (6.9) 8.8°C (16°F) 16.6 (57000) 16.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity kW (BTU/hr) Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 43.33°C DB, 22.4°C WB (110°F DB, 72°F WB) 7.7°C (14°F) 38.5 (131000) 37.8 (12900) 0.98 1.24 (19.6) 75.8 (25.4) 8.8°C (16°F) 37.0 (126000) 36.3 (124000) 0.98 1.04 (16.4) 55.7 (18.7) 10°C (18°F) 35.7 (122000) 35.0 (119000) 0.98 0.89 (14.1) 42.6 (14.3) 11.1°C (20°F) 34.5 (118000) 33.
Performance Specifications 7.2°C (45°F) EWT (ACRC301S) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 18.4 (63000) 18.2 (62000) 0.99 0.84 (13.3) 38.7 (13.0) 6.6°C (12°F) 16.6 (57000) 16.5 (56000) 0.99 0.62 (9.8) 22.3 (7.5) 7.7°C (14°F) 15.2 (52000) 15.1 (51000) 0.99 0.50 (8.0) 15.2 (5.1) 8.8°C (16°F) 13.8 (47000) 13.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio SHR CW Flow Rate Total CW Pressure Drop l/s (GPM) kPa (ft H2O) kW (BTU/hr) kW (BTU/hr) 7.7°C (14°F) 35.8 (122000) 35.4 (121000) 0.99 1.15 (18.2) 66.9 (22.4) 8.8°C (16°F) 34.4 (117000) 34.0 (116000) 0.99 0.96 (15.3) 49.1 (16.5) 10°C (18°F) 33.1 (113000) 32.8 (112000) 0.99 0.82 (13.0) 37.1 (12.5) 11.1°C (20°F) 31.9 (109000) 31.6 (108000) 0.99 0.72 (11.4) 29.2 (9.8) 7.
Performance Specifications 8.8°C (48°F) EWT (ACRC301S) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 16.2 (55000) 16.0 (55000) 0.99 0.75 (11.8) 31.4 (10.5) 6.6°C (12°F) 14.6 (50000) 14.5 (49000) 0.99 0.56 (8.8) 17.9 (6.0) 7.7°C (14°F) 13.2 (45000) 13.1 (45000) 0.99 0.44 (7.0) 11.7 (3.9) 8.8°C (16°F) 11.9 (41000) 11.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 7.7°C (14°F) 33.8 (115000) 33.4 (114000) 0.99 1.09 (17.2) 60.6 (20.3) 8.8°C (16°F) 32.4 (111000) 32.1 (110000) 0.99 0.91 (14.4) 44.5 (14.9) 10°C (18°F) 31.2 (106000) 30.9 (105000) 0.99 0.78 (12.3) 33.7 (11.3) 11.1°C (20°F) 30.0 (102000) 29.7 (101000) 0.99 0.68 (10.7) 26.4 (8.9) 7.
Performance Specifications 10°C (50°F) EWT (ACRC301S) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 14.6 (50000) 14.6 (50000) 1.00 0.67 (10.7) 26.2 (8.8) 6.6°C (12°F) 13.1 (45000) 13.1 (45000) 1.00 0.48 (7.7) 13.6 (4.6) 7.7°C (14°F) 11.7 (40000) 11.7 (40000) 1.00 0.39 (6.2) 9.2 (3.1) 8.8°C (16°F) 10.7 (36000) 10.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 33.5 (114000) 33.5 (114000) 1.00 1.26 (20.0) 78.9 (38.7) 7.7°C (14°F) 32.3 (110000) 32.3 (110000) 1.00 1.04 (16.5) 56.0 (18.8) 8.8°C (16°F) 31.0 (106000) 31.0 (106000) 1.00 0.87 (13.8) 41.0 (13.8) 10°C (18°F) 29.7 (101000) 29.7 (101000) 1.00 0.74 (11.) 31.1 (10.4) 11.
Performance Specifications 12.7°C (55°F) EWT (ACRC301S) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 11.0 (37000) 11.0 (37000) 1.00 0.51 (8.2) 15.9 (5.3) 6.6°C (12°F) 9.6 (33000) 9.6 (33000) 1.00 0.38 (6.0) 8.5 (2.9) 7.7°C (14°F) 8.3 (28000) 8.3 (28000) 1.00 0.28 (4.5) 4.2 (1.4) 5.5°C (10°F) 14.4 (49000) 14.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 30.3 (103000) 30.3 (103000) 1.00 1.14 (18.0) 65.5 (22.0) 7.7°C (14°F) 28.9 (99000) 28.9 (99000) 1.00 0.93 (14.8) 46.3 (15.5) 8.8°C (16°F) 27.7 (94000) 27.7 (94000) 1.00 0.78 (12.4) 34.1 (11.4) 10°C (18°F) 26.5 (90000) 26.5 (90000) 1.00 0.66 (10.5) 25.5 (8.5) 11.
Performance Specifications 15°C (59°F) EWT (ACRC301S) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Heat Sensible Net Capacity Sensible Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 7.9 (27000) 7.9 (27000) 1.00 0.38 (6.0) 8.5 (2.9) 6.6°C (12°F) 7.0 (24000) 7.0 (24000) 1.00 0.28 (4.4) 5.3 (1.8) 5.5°C (10°F) 11.3 (39000) 11.3 (39000) 1.00 0.53 (8.4) 16.8 (5.6) 6.6°C (12°F) 10.4 (36000) 10.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Heat Sensible Net Capacity Sensible Ratio CW Flow Rate Total CW Pressure Drop l/s (GPM) kPa (ft H2O) kW (BTU/hr) kW (BTU/hr) SHR 5.5°C (10°F) 28.3 (97000) 28.3 (97000) 1.00 1.28 (20.3) 80.5 (27.0) 6.6°C (12°F) 27.3 (93000) 27.3 (93000) 1.00 01.03 (16.4) 55.4 (18.6) 7.7°C (14°F) 26.0 (89000) 26.0 (89000) 1.00 0.84 (13.3) 38.6 (13.0) 8.8°C (16°F) 24.9 (85000) 24.9 (85000) 1.00 0.70 (11.2) 28.3 (9.
ACRC301H Performance Specifications 10°C (50°F) EWT Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 23.0 (79000) 23.0 (79000) 1.00 1.12 (17.8) 31.3 (10.5) 6.6°C (12°F) 21.5 (73000) 21.5 (73000) 1.00 0.88 (14.0) 20.0 (6.7) 7.7°C (14°F) 19.8 (68000) 19.8 (68000) 1.00 0.70 (11.1) 13.0 (4.4) 8.8°C (16°F) 18.1 (62000) 18.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 48.2 (164000) 48.2 (164000) 1.00 1.92 (30.4) 88.3 (29.6) 7.7°C (14°F) 46.7 (159000) 46.7 (159000) 1.00 1.57 (24.9) 58.7 (19.7) 8.8°C (16°F) 45.3 (155000) 45.3 (155000) 1.00 1.33 (21.1) 43.1 (14.5) 10°C (18°F) 43.8 (149000) 43.8 (149000) 1.00 1.14 (18.1) 32.4 (10.9) 11.
Performance Specifications 12.7°C (55°F) EWT (ACRC301H) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 17.9 (61000) 17.9 (61000) 1.00 0.89 (14.1) 20.3 (6.8) 6.6°C (12°F) 16.2 (55000) 16.2 (55000) 1.00 0.68 (10.8) 12.4 (4.2) 7.7°C (14°F) 14.5 (49000) 14.5 (49000) 1.00 0.53 (8.3) 7.8 (2.6) 8.8°C (16°F) 12.7 (43000) 12.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 48.9 (167000) 48.9 (167000) 1.00 1.93 (30.5) 86.7 (29.1) 7.7°C (14°F) 47.4 (162000) 47.4 (162000) 1.00 1.55 (24.6) 57.6 (19.3) 8.8°C (16°F) 46.0 (157000) 46.0 (157000) 1.00 1.35 (21.5) 44.5 (14.9) 10°C (18°F) 44.5 (152000) 44.5 (152000) 1.00 1.18 (18.7) 34.4 (11.5) 11.
Performance Specifications 15°C (59°F) EWT (ACRC301H) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop SHR l/s (GPM) kPa (ft H2O) kW (BTU/hr) kW (BTU/hr) 5.5°C (10°F) 13.4 (46000) 13.4 (46000) 1.00 0.69 (10.9) 12.6 (4.2) 6.6°C (12°F) 11.4 (39000) 11.4 (39000) 1.00 0.49 (7.7) 6.6 (2.2) 7.7°C (14°F) 9.7 (33000) 9.7 (33000) 1.00 0.37 (5.9) 4.2 (1.4) 5.5°C (10°F) 18.0 (61000) 18.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 44.6 (152000) 44.6 (152000) 1.00 1.81 (28.6) 76.6 (25.7) 7.7°C (14°F) 43.2 (147000) 43.2 (147000) 1.00 1.51 (23.9) 54.5 (18.3) 8.8°C (16°F) 41.6 (142000) 41.6 (142000) 1.00 1.23 (19.6) 37.4 (12.5) 10°C (18°F) 40.1 (137000) 40.1 (137000) 1.00 1.05 (16.7) 27.8 (9.3) 11.
Performance Specifications 17.5°C (63.5°F) EWT (ACRC301H) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 8.3 (28000) 8.3 (28000) 1.00 0.46 (7.3) 6.1 (2.0) 6.6°C (12°F) 6.3 (22000) 6.3 (22000) 1.00 0.30 (4.8) 2.9 (1.0) 5.5°C (10°F) 13.3 (45000) 13.3 (45000) 1.00 0.68 (10.8) 12.5 (4.2) 6.6°C (12°F) 11.6 (40000) 11.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 45.3 (154000) 45.3 (154000) 1.00 1.77 (28.1) 73.8 (24.7) 7.7°C (14°F) 44.0 (150000) 44.0 (150000) 1.00 1.48 (23.5) 52.8 (17.7) 8.8°C (16°F) 42.5 (145000) 42.5 (145000) 1.00 1.25 (19.9) 38.6 (12.9) 10°C (18°F) 41.1 (140000) 41.1 (140000) 1.00 1.08 (17.1) 29.0 (9.7) 11.
Performance Specifications 20°C (68°F) EWT (ACRC301H) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Heat Sensible Net Capacity Sensible Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 8.4 (29000) 8.4 (29000) 1.00 0.46 (7.3) 6.2 (2.1) 6.6°C (12°F) 6.5 (22000) 6.5 (22000) 1.00 0.31 (4.9) 3.0 (1.0) 5.5°C (10°F) 14.4 (49000) 14.4 (49000) 1.00 0.74 (11.7) 14.4 (4.8) 6.6°C (12°F) 12.5 (43000) 12.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Heat Sensible Net Capacity Sensible Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 40.4 (138000) 40.4 (138000) 1.00 1.58 (25.0) 59.2 (19.9) 7.7°C (14°F) 39.2 (134000) 39.2 (134000) 1.00 1.23 (19.5) 37.0 (12.4) 8.8°C (16°F) 37.8 (129000) 37.8 (129000) 1.00 1.13 (17.8) 31.5 (10.6) 10°C (18°F) 36.4 (124000) 36.4 (124000) 1.00 0.96 (15.2) 23.4 (7.9) 11.
Performance Specifications 22°C (72°F) EWT (ACRC301H) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Heat Sensible Net Capacity Sensible Ratio SHR CW Flow Rate Total CW Pressure Drop l/s (GPM) kPa (ft H2O) kW (BTU/hr) kW (BTU/hr) 5.5°C (10°F) 10.8 (37000) 10.8 (37000) 1.00 0.57 (9.0) 9.0 (3.0) 6.6°C (12°F) 9.0 (31000) 9.0 (31000) 1.00 0.41 (6.4) 4.9 (1.6) 7.7°C (14°F) 6.9 (24000) 6.9 (24000) 1.00 0.28 (4.4) 2.5 (0.8) 5.5°C (10°F) 16.6 (57000) 16.6 (57000) 1.
Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Heat Sensible Net Capacity Sensible Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 42.2 (144000) 42.2 (144000) 1.00 1.61 (25.5) 63.6 (21.3) 7.7°C (14°F) 41.0 (140000) 41.0 (140000) 1.00 1.38 (21.9) 46.3 (15.5) 8.8°C (16°F) 39.7 (136000) 39.7 (136000) 1.00 1.18 (18.7) 34.5 (11.6) 10°C (18°F) 38.3 (131000) 38.3 (131000) 1.00 1.01 (16.0) 25.8 (8.7) 11.
ACRC500 Series/ACRP500 Series Performance Specifications 5.6°C (42°F) EWT Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Sensible Sensible Net Capacity Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 6.6°C (12°F) 44.3 (151000) 40.7 (139000) 0.92 1.6 (25.9) 66 (21.95) 7.7°C (14°F) 40.8 (139000) 37.9 (129000) 0.93 1.3 (20.6) 42 (14.1) 8.8°C (16°F) 37.8 (129000) 35.2 (120000) 0.93 1.1 (16.8) 29 (9.5) 26.7°C DB, 17.
Performance Specifications 7.2°C (45°F) EWT (ACRC500/ACRP500) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity kW (BTU/hr) Heat Sensible Net Capacity Sensible Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB) 5.5°C (10°F) 40.8 (139000) 39.6 (135000) 0.97 1.8 (28.8) 81 (27.03) 6.6°C (12°F) 37.9 (130000) 36.8 (126000) 0.97 1.4 (22.5) 50 (16.6) 7.7°C (14°F) 35.1 (120000) 34.1 (116000) 0.97 1.
Performance Specifications 8.8°C (48°F) EWT (ACRC500/ACRP500) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity kW (BTU/hr) Heat CW Flow Rate Sensible Net Capacity Sensible Ratio Total CW Pressure Drop kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB) 5.5°C (10°F) 35.7 (122000) 34.6 (118000) 0.97 1.6 (25.5) 63 (21.3) 6.6°C (12°F) 32.9 (112000) 31.9 (109000) 0.97 1.2 (19.7) 39 (12.9) 7.7°C (14°F) 30.3 (103000) 29.4 (100000) 0.97 1.0 (15.
Performance Specifications 10°C (50°F) EWT (ACRC500/ACRP500) Temperature DB, WB °C (°F) CW Delta T °C (°F) Model Series Net Total Net Capacity Sensible Capacity Sensible Heat Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB) 5.5°C (10°F) ACRC500/ACRP500 32.6 (111000) 31.8 (109000) 0.98 1.5 (23.5) 54 (18.02) 6.6°C (12°F) ACRC500/ACRP500 29.9 (102000) 29.2 (100000) 0.98 1.1 (18.1) 33 (11.1) 7.
Performance Specifications 12.7°C (55°F) EWT (ACRC500/ACRP500) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity kW (BTU/hr) Heat Sensible Net Capacity Sensible Ratio CW Flow Rate Total CW Pressure Drop kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB) 5.5°C (10°F) 24.7 (85000) 24.7 (85000) 1.00 1.2 (18.3) 33 (11.3) 6.6°C (12°F) 22.3 (76000) 22.3 (76000) 1.00 0.9 (13.9) 20 (6.7) 7.7°C (14°F) 20.0 (68000) 20.0 (68000) 1.00 0.7 (10.
Performance Specifications 15.5°C (60°F) EWT (ACRC500/ACRP500) Temperature DB, WB °C (°F) CW Delta T °C (°F) Total Net Capacity Heat CW Flow Rate Total CW Pressure Sensible Net Capacity Sensible Ratio Drop kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O) 5.5°C (10°F) 17.5 (60000) 17.5 (60000) 1.00 0.9 (13.5) 19 (6.2) 6.6°C (12°F) 15.2 (52000) 15.2 (52000) 1.00 0.6 (10.0) 11 (3.7) 7.7°C (14°F) 13.1 (45000) 13.1 (45000) 1.00 0.5 (7.6) 6 (2.1) 8.8°C (16°F) 11.1 (38000) 11.
Performance Data—General ACRC301S MODULATING VALVES Size 3 Way Ball Valve – NPT mm (in.) (Cv) 25.4 (1) (30.8) AIR SYSTEM 200-mm (7.9-in) MIXED FLOW DIRECT DRIVE DC TUBEAXIAL FANS Air Volume - l/s (SCFM) Fan Motor - Watts (each) Number of Fans Performance Specifications Table Multiplier* Standard Filter 51-mm (2-in.) Pleated Filter 1510 (3200) 112.5 8 1345 (2850) 122.5 8 1.0 .94 WATER TEMPERATURE Minimum Entering Temperature - ºC (ºF) Maximum Entering Temperature - ºC (ºF) 5 (41) 15 (55.
ACRC301H** MODULATING VALVES Size 3-Way Ball Valve – NPT mm (in.) (Cv) 31.75 (1 1/4) (34.1) AIR SYSTEM 200-mm (7.9-in.) MIXED FLOW DIRECT DRIVE DC TUBEAXIAL FANS Air Volume - l/s (SCFM) Fan Motor - Watts (each) Number of Fans Performance Specifications Table Multiplier* Standard Filter 51-mm (2-in.) Pleated Filter 1982 (4200) 225 8 1793 (3800) 240 8 1.0 .94 WATER TEMPERATURE Minimum Entering Temperature - ºC (ºF) Maximum Entering Temperature - ºC (ºF) 10 (50) 22 (71.
ACRC500/ACRP500 series MODULATING VALVES Size 3-Way Ball Valve - NPT mm (in.) 25.4 (1) AIR SYSTEM 400-mm (15.8-in) BACKWARD INCLINE DIRECT DRIVE FANS (Standard Filter Installed) Air Volume - l/s (SCFM) Fan Motor - kW (HP) Number of Fans 2832 (6000) 1.00 (1.5) 3 COOLING COIL - COPPER TUBE/ALUMINUM FIN Face Area - m2 (ft2) Rows Deep FPM (FPI) 0.74 (7.9) 4 468 (12) FILTERS - PLEATED (STANDARD) Quantity Size - mm (in.) Depth - mm (in.) Efficiency (%) 4 418 x 470 (16.45 x 18.5) 101.
Glycol Correction Factors Performance Criteria Capacity* Pressure Drop** Percent Volume of Solution *** Glycol Solution 0 10% 20% 30% 40% 50% Ethylene Propylene Ethylene Propylene 1.00 1.00 1.00 1.00 0.96 0.98 1.04 1.10 0.94 0.97 1.14 1.23 0.91 0.94 1.24 1.43 0.87 0.91 1.36 1.67 0.84 0.88 1.50 1.92 Values are derived using the Darcy-Weisbach pressure drop equation at 50°F and 1 atmosphere and Type L copper pipe.
Sound Performance Data ACRC301S Series Tested Sound Data Fan Speed% 30 40 60 80 100 Airflow l/s (SCFM) 430 (900) 610 (1300) 940 (2000) 1270 (2700) 1510 (3200) Sound Power dB at Frequency Hz re: 10-12W Lp Sound Pressure dB 20 μPa* dBA dBA 64.8 69.6 78.2 87.5 90.5 49.8 56.4 65.4 73.8 77.1 *Sound tested at 1.8 m (6 ft) distance from the unit and 1 m (3.3 ft) from the floor.
Electrical Data Model Power Voltage Phase MCA MOP FLA Frequency Power kW Power Connection NEMA L5-20P 100–120 1 50/60 N/A N/A 11A 1 ACRC301S IEC-309-16A 200–240 1 50/60 N/A N/A 11A 1 208–230 1 50/60 15A 15A 12A 1.9** Hardwired Dew point 208–230 control pump 1 50/60 N/A N/A 1.6A 0.025– 0.31 N/A ACRC301H NEMA L21-20P ACRC500* 200–240 3 50/60 11 15 N/A 3.2 (Top-Wired Only) ACRC501 460–480 3 50/60 7 15 N/A 3.
Dimensional Data InRow ACRC301 series assembled module 1991 ( na4339a 78.39) 1095 ( 43.11) 1.80) 300 (1 *Dimensions shown in mm (in.) InRow ACRC500/ACRP500 series assembled module 42.13) 1070 ( 600 (2 3.62) 78.39) na1849a 1991 ( *Dimensions shown in mm (in.
SX to VX height adapter—ACRC301S/ACRC301H series *Dimensions shown in mm (in.) SX to 48U SX height adapter—ACRC301S/ACRC301H series *Dimensions shown in mm (in.) SX to VX height adapter—ACRC500/ACRP500 seriesSX to 48U SX height adapter— *Dimensions shown in mm (in.) ACRC500/ACRP500 series *Dimensions shown in mm (in.
Piping Connections Piping and electrical access - ACRC301S 110 (4.31) 83 (3.27) 204 (8.02) 116 (4.55) 110 (4.35) 180 (7.10) 97 (3.83) 145 (5.72) 147 (5.80) 56 (2.22) TOP 184 (7.26) 240 (9.46) 199 (7.85) 157 (6.20) na4353a 189 (7.43) 174 (6.84) 53 (2.08) 90 (3.54) 161 (6.34) BOTTOM (LOOKING UP) * Dimensions are shown in mm (in.).
BOTTOM LOOKING UP na4463a TOP Item 70 Description Power connections Condensate line—0.25 in. ID/0.38 in. OD 1-in. NPT female return pipe (outlet) 1-in. NPT female supply pipe (inlet) Low voltage input wiring.
Piping and electrical access - ACRC301H 81 (3.19) 233 (9.17) 132 (5.21) 193 (7.60) 116 (4.55) 152 (6.00) 97 (3.83) 126 (4.95) 61 (2.38) TOP 170 (6.69) 130 (5.12) 240 (9.46) 280 (11.02) na4334a 156 (6.14) 158 (6.23) 56 (2.22) 224 (8.82) BOTTOM (LOOKING UP) * Dimensions are shown in mm (in).
BOTTOM LOOKING UP na4464a TOP Item 72 Description Power connections 1 1/4-in. NPT female return pipe (outlet) 1 1/4-in.
na4343a Internal piping diagram - ACRC301S Item Description Item Description Outlet water union (top piping option) Outlet water union (bottom piping option) Inlet water union (top piping option) Inlet water union (bottom piping option) 3-way actuator control valve—1 in. Drain valve Flow meter Condensate pump Bypass shutoff ball valve—3/4 in. Bottom condensate pan Inlet shutoff valve—1 in.
na4358a Internal piping diagram - ACRC301H Item 74 Description Item Description Outlet water union (top piping option) Outlet water union (bottom piping option) Inlet water union (top piping option) Inlet water union (bottom piping option) 3-way actuator control valve—1 1/4 in. Coil Flow meter Circulation pump (optional) Bypass shutoff valve—1 in. Circulation pump check valve (optional) Inlet shutoff valve—1 1/4 in.
ACRC301 series With Cooling Distribution Unit (CDU) A CDU is only used with ACRC301S units.
Without CDU TOP PIPING TO CUSTOMER SUPPLIED CHILLER BOTTOM PIPING TO CUSTOMER SUPPLIED CHILLER INROW RC Flex hose or copper Strainer with 20 mesh screen (field installed) Copper tubing Shutoff valve (field-installed) Circuit setter 76 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
ACRC500/ACRP500 series Top piping without CDU To customersupplied chiller RC Bottom piping without CDU RC To customersupplied chiller Item Description Item Description Flexible piping adapters* Shutoff valve (field-installed) Balancing valve (field-installed) Y-strainer with 20-mesh screen (field-installed)** *Recommended at these locations when the equipment is connected to rigid piping. Consult local codes for proper installation.
ACRC500/ACRP500 Series Top chilled water piping access (top view) NOTE: Top or bottom entry can be chosen individually for each type of connection, i.e. power, condensate drain, humidifier water supply, chilled water supply and chilled water return. Top piping configuration will have the same valves and strainers as bottom piping configuration. REAR—HOT AISLE FRONT—COLD AISLE Note: Dimensions are shown in mm (in.).
Bottom piping and power access locations (bottom view, looking up) REAR—HOT AISLE FRONT—COLD AISLE Item 990-4618C-001 Description Humidifier supply (ACRP500 series only) Condensate drain Power connections—dual feed Communication connections Condensate overflow NPSM (supply/inlet) from chiller NPSM (return/outlet) to chiller InRow Chilled Water Air Conditioners Technical Specifications 79
Facility Planning Model ACRC 301S ACRC 301H ACRC 500 ACRC 501 ACRC 502 ACRP 500 ACRP 501 ACRP 502 Input Voltage 100–240 208–230 200–240 460–480 380–415 200–240 460–480 380–415 1 1 3 3 3 3 3 3 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 Total NET Capacity – kW (BTU/hr)* 23.5 (80,000) 39.0 (133,000) 45 (154,000) 45 (154,000) 45 (154,000) 45 (154,000) 45 (154,000) 45 (154,000) Sensible NET Capacity – kW (BTU/hr) * 23.5 (80,000) 39.0 (133,000) 43.
Model ACRC 301S ACRC 301H ACRC 500 ACRC 501 ACRC 502 ACRP 500 ACRP 501 ACRP 502 Optional Filter Type 2-in. Pleated 2-in.
Warranty Three-Phase Power Products or Cooling Solutions One-Year Factory Warranty The limited warranty provided by Schneider Electric™ in this Statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your business.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.
Guide Specifications InRow RC® Chilled Water Cooling Units 100-240V/1ph/50/60Hz (ACRC301S) 208-230V/1ph/50/60Hz (ACRC301H) 200-240V/3ph/50/60Hz (ACRC500/ACRP500) 460-480V/3ph/50/60Hz (ACRC501/ACRP501) 380-415V/3ph/50/60Hz (ACRC502/ACRP502) THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE ARCHITECT OR THE ENGINEER TO MEET THE REQUIREMENTS OF THE PROJECT.
1.2 A. DESIGN REQUIREMENTS The system shall be as described in the following specification as manufactured by Schneider Electric. 1. Model: __________________________________________. 2. Total net cooling capacity: ___________________________ MBH (kW). 3. Sensible net cooling capacity: ________________________ MBH (kW). 4. Return air temperature: _____________________________ ºC (ºF) DB. 5. Return air temperature: _____________________________ ºC (ºF) WB. 6.
PART 2 — PRODUCT 2.1 STANDARD COMPONENTS A. CABINET CONSTRUCTION 1. Exterior panels shall be 18 gauge steel with 5 lb/ft3 (80 kg/m3) density foam insulation. Insulation complies with UL94 HF-1. Front and rear exterior panels shall be 18 gauge perforated steel with 80% open free area, and equipped with a keyed lock to provide a means of securing access to the internal components of the unit. 2. The frame shall be constructed of 16 gauge formed steel welded for maximum strength.
C. AUTOMATIC TRANSFER SWITCH 1. The unit shall be equipped with an automatic transfer switch (ATS). The ATS shall automatically switch from a main power supply to a secondary power supply in the event of a power outage without change in equipment operation. The ATS shall monitor the main power supply so that when power is restored to the primary source it will automatically switch from the secondary source back to the main power source. D. MAIN DISCONNECT SWITCH 1. ACRC301S & ACRC301H a.
F. PRIMARY/SECONDARY POWER INPUT 1. Input Power Feeds a. Primary/secondary power inputs should be a locking NEMA or IEC plug (ACRC301S, ACRC500, and ACRC502) or hardwired connection (ACRC301H, ACRC500 series, and ACRP500 series) suitable for the input power selected. b. Each power input shall be capable of running the unit at 100% capacity in the event of a main power failure. G. MICROPROCESSOR CONTROLLER 1. Monitoring and Configuration: a.
23. Fan Power Supply Fault (ACRC301 series only) 24. Fan run hours exceeded (ACRC500/ACRP500 series only) 25. Condensate run hours exceeded (ACRC500/ACRP500 series only) 26. Humidifier water conductivity high violation (ACRP500 series only) 27. Humidifier fault tolerance exceeded (ACRP500 series only) 28. Humidifier low water (ACRP500 series only) 29. Humidifier excessive output reduction (ACRP500 series only) 30. Humidifier drain fault (ACRP500 series only) 31.
minimum of 0.016-in. thick. Coil tube sheets shall be a minimum 18 gauge G90 galvanized steel. The coil shall be rated for a maximum pressure of 2757.9 kPa (400 psig). Coil headers are equipped with drip plates in the bottom to route the condensate accumulating on the header tubes to the condensation pan. The coil is configured in a counterflow arrangement to optimize heat transfer efficiency 4. Cooling Fluids a. Chilled water and solutions of propylene or ethylene glycol up to 50% may be used.
a maximum lift of 4.9 m (16 ft). Dual floats are included with the unit. One float is used for condensate pump control; the other is to generate condensate pan overflow alarms. 2. ACRC500/ACRP500 Series a. The factory-installed condensate pump is piped internally to the condensate pan. It is capable of pumping 31.8 l/h (8.45 GPH) liquid a maximum distance of 18 m (60 ft), which may include a maximum lift of 3.5 m (11.5 ft). Dual floats are included with the unit.
3. Heaters shall be provided with self-engaging electrical connectors upon installation. Heaters with manually connected conductors are not acceptable. Q. TEMPERATURE AND HUMIDITY SENSORS 1. ACRC301S/ACRC301H a. Internal Sensors 1. Internal Temperature Sensors: Thermister temperature sensors shall be mounted behind the front and rear doors to provide control inputs based on supply and return air temperature. Sensor accuracy shall be within +/- 2ºF accuracy. 2.
S. FLOW METER 1. The flow meter shall be factory piped inside the unit and connected to microprocessor controls to provide water flow rate through the unit. The microprocessor controller shall also use this information to provide total unit capacity out of the unit while in operation. 2. The flow meter shall be a glass filled nylon construction vortex-sensing meter, compatible with glycol/water solutions up to 50% with accuracy of 2.5% FS @ 10–200 LPM (2.6–53 GPM). T. PIPING 1.
PART 3 — EXECUTION 3.1 A. GUIDELINES FOR INSTALLATION GENERAL 1. The InRow RC provides reliable, accurate temperature control of computer rooms, laboratories, and other environments that require close tolerance control. The unit incorporates the latest system design innovations to provide you with optimum efficiency, reliability, and accuracy of control. 2. The InRow RC unit will provide years of trouble-free service, when installed and maintained by technically qualified personnel.
2. When using a forklift to move the unit, use the shipping skid to protect the bottom of the unit. When using chains, cables, or rope to lift the unit, use spreader bars to prevent damage to the finished panels. Four threaded M10x16 holes are provided to accommodate lifting eye bolts that can be utilized to lift the unit. 3. Exercise caution when maneuvering and transporting the cooling unit as it can tip easily. F. CONDENSATE DRAIN ROUTING 1.
Worldwide Customer Support Customer support is available at no charge via e-mail or telephone. Contact information is available at www.schneiderelectric.com/. Select Support > Operations around the world. © Schneider Electric is owned by Schneider Electric Industries S.A.S., or its affiliated companies. All other trademarks are property of their respective owners.