Datasheet

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
11
a. Normal Operation
b. Battery Operation
c. Bypass Operation
d. Common Fault
e. Low Battery
f. UPS Off
H. Communication Interface Board: A communication interface board shall provide the
following communication ports which can be used simultaneously:
1. RS232 Serial Port #1
2. RJ-45 Interface port for a Remote Display
2.8 BATTERY
A. The UPS battery shall be of modular construction made up of user replaceable, hot
swappable, fused, battery modules. Each battery module shall be monitored for voltage
and temperature for use by the UPS battery diagnostic, and temperature compensated
charger circuitry.
B. The battery jars housed within each removable battery module shall be of the Valve
Regulated Lead Acid (VRLA) type.
C. The UPS shall incorporate a battery management system to continuously monitor the
health of each removable battery module. This system shall notify the user in the event
that a failed or weak battery module is found.
PART 3 – ACCESSORIES
3.1 BATTERY DISCONNECT BREAKER
A. Each UPS system shall have a 250 VDC rated, thermal magnetic trip molded case
circuit breaker. Each circuit breaker shall be equipped shunt trip mechanisms and
1A/1B auxiliary contacts. The circuit breakers are to be located within the UPS
enclosure or as part of a line-up-and-match type battery cabinet.
3.2 MAINTENANCE BYPASS PANEL
A. The UPS cabinet shall include an integrated three-switch maintenance bypass panel
(MBP). The MBP shall provide power to the critical load from the bypass source,
during times where maintenance or service of the UPS is required. The PDU/System
bypass shall provide a mechanical means of complete isolation of the UPS from the
critical output distribution.