CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
15
Seismic rated floor stands shall be available to take the place of supporting the
PDU/system bypass, UPS, and Battery Enclosures on a raised floor environment. Floor
Stands shall be available in custom heights to maintain a flush mount installation
adjacent to the raised floor, and shall be designed in accordance to the equipment
weight and contact points.
3.11 SOFTWARE AND CONNECTIVITY
A. Network Adaptor: The Ethernet Web/SNMP Adaptor shall allow one or more
network management systems (NMS) to monitor and manage the UPS in TCP/IP
network environments. The management information base (MIB) shall be provided in
DOS and UNIX "tar" formats. The SNMP interface adaptor shall be connected to the
UPS via the RS232 serial port on the standard communication interface board.
B. Unattended Shutdown
1. The System, in conjunction with a network interface card, shall be capable of
gracefully shutting down one or more operating systems during when the UPS is
on reserve mode.
2. The System shall also be capable of using an RS232 port to communicate by
means of serial communications to gracefully shut down one or more operating
systems during an on battery situation.
3.12 REMOTE SYSETEM MONITORING
A. The following three methods of remote UPS monitoring shall be available:
1. Web Monitoring: Remote monitoring shall be available via a web browser such as
Internet Explorer.
2. RS232 Monitoring: Remote UPS monitoring shall be possible via either RS232
or contact closure signals from the UPS.
3. Simple Network Management Protocol (SNMP): Remote UPS Monitoring shall be
possible through a standard MIB II compliant platform.
3.13 SOFTWARE COMPATIBILITY
A: The UPS manufacturer shall have available software to support graceful
shutdown and remote monitoring for the following systems:
a. Microsoft Windows 95/98/XP
b. Microsoft Windows NT 4.0 SP6/2000
c. OS/2
d. Netware 3.2 – 5.1
e. MAC OS 9.04, 9.22, 10
g. Digital Unix/True 64
h. SGI 6.0-6.5