CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
3
2. Product catalog sheets or equipment brochures.
3. Product guide specifications.
4. System single-line operation diagram.
5. Installation information, including weights and dimensions.
6. Information about terminal locations for power and control connections.
7. Drawings and details for requested optional accessories.
B. Delivery Submittals:
1. Installation manual, which includes instructions for storage, handling,
examination, preparation, installation, and start-up of UPS.
2. User manual, which includes operating instructions.
3. As built equipment drawings
4. InfraStruXure
TM
Welcome Package.
PART 2 – PRODUCT
2.1 DESIGN REQUIREMENTS
A. The UPS shall be sized for _____ kVA and _____ kW load.
B. The UPS battery shall be sized for _____ at a Power Factor of_____ for _____ minutes.
2.2 SYSTEM CHARACTERISTICS
A. System Capacity: The system shall be rated for full kW output in the following frame
sizes:
1. 20 kVA/kW - Can be configured with up to (3), 10kW power modules for N+1
B. Input:
1. AC Input Nominal Voltage: 208 V, 3 Phase, 4 wire, 50/60 Hz.
2. AC Input Voltage Window:
+
/
-
15% of nominal (while providing nominal
charging to the battery system).