CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
4
3. Short Circuit Withstand Rating: 30,000 Symmetrical Amperes
4. Maximum Frequency Range: 40-70Hz
5. Input Power Factor:
a. > .96 at 50% load
b. > .99 at 100% load
6. Input Current Distortion with no additional filters:
a. < 6% at 100% load
b. < 6% at 50% load
7. Soft-Start: Shall be linear from 0-100% input current and shall not exhibit inrush.
This shall take place over a 15 second time period
C. UPS Output:
1. AC Output Nominal Voltage: 208V, 3 Phase, 4 wire, 60 Hz.
2. AC Output Voltage Distortion: Max. 3% @ 100% Linear Load.
3. AC Output Voltage Regulation:
+
/- 1% For 100 % Linear or Nonlinear Load
4. Voltage Transient Response:
+
/
-
5% maximum for 100% load step
5. Voltage Transient Recovery within <60 milliseconds
6. Output Voltage Harmonic Distortion:
a. <2% THD maximum and 1% single harmonic for a 100% linear load
b. <5% THD maximum for a 100% non-linear load
7. Phase Angle Displacement:
a. 120 degrees
+
/
-
1 degree for balanced load
b. 120 degrees
+
/
-
1 degrees for 50% imbalanced load
c. 120 degrees
+
/
-
3 degrees for 100% imbalanced load
8. Overload Rating:
a. Normal Operation:
1) 150% for 30 seconds
2) <105% continuous
b. Bypass Operation:
1) 125% continuous