Specifications

NetShelter SX Enclosure — Unpacking, Installation, and Customization Manual14
Grounding the Enclosure
Each enclosure should be bonded directly to a common ground using one of the designated grounding
locations (two M6 threaded inserts) at the top or bottom of the enclosure.
Use a Common Bonding Network Jumper kit (for example, Listed [KDER] Panduit
®
RGCBNJ660PY or equivalent)
Use paint-piercing washers between ground terminal and enclosure frame or remove paint on
frame under ground terminals per NEC NFPA 70 Article 250.12
Torque screws to 6.9 N-m (60 in-lb)
Bonding Locations on the Enclosure
ns1617b