Specifications
15NetShelter SX Enclosure — Unpacking, Installation, and Customization Manual
Equipment Installation
Note: APC NetShelter SX enclosures are intended for use with Listed equipment. If you
install un-Listed equipment, you should evaluate the safety of your configuration.
Adjusting Vertical Mounting Flanges
Vertical mounting flanges come factory-installed in the proper
location for use with rack-mountable equipment that has a depth
of 737 mm (29 in). The mounting flanges are adjustable towards
the front or the rear of the enclosure to accommodate different
rails or equipment with other depths.
• The mounting flanges on a 600 mm (23.6 in) wide
enclosure can be adjusted to be as close
as 191 mm (7.50 in) or as far as 935 mm (36.80 in) apart.
• The mounting flanges on a 750 mm (29.5 in) wide
enclosure can be adjusted to be as close as 292.10 mm
(11.50 in) or as far as 787.40 mm (31 in) apart.
A common application for the 750 mm (29.5 in) wide enclosure
is to move the flanges to a depth of 476 mm (18.75 in) to
accommodate networking and telecommunications equipment.