Surge Protective Devices (SPD) APC Brick Panel Products Installation and Operation Manual The Brick Panel Product Surge Protective Devices (SPD) are designed to provide protection at the service entrance, branch panels or other critical locations for today’s electrical equipment. The APC SurgeArrest® Brick Panel Mount Products have replaceable multi-phase modules, a display panel with surge counter and LED status indicators, an audible alarm, and a NEMA 1 Enclosure.
WARNINGS APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. · This equipment must only be installed and serviced by qualified electrical personnel. · Turn off all power supplying this equipment before working on or inside equipment. · Always use a properly rated voltage sensing device to confirm power is off.
APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) WARNINGS CAUTION LOSS OF SURGE PROTECTION · During installation into an electrical system, SPDs must not be energized until the electrical system is completely installed, inspected, and tested. All conductors must be connected and functional, including the neutral. The voltage rating of the device and system must always be verified before energizing the surge protective device.
TABLE OF CONTENTS APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) SurgeArrest® Brick PM Series CONTENTS INTRODUCTION ............................................................................. 5 UNPACKING AND PRELIMINARY INSPECTION.............................. 6 STORAGE ....................................................................................... 6 SAFETY LABELS ............................................................................ 7 SPD LOCATION CONSIDERATIONS ..................
APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) INTRODUCTION INTRODUCTION Thank you for choosing the APC SurgeArrest® PM2Z or PM3X Series “Brick” Surge Protection Device. The APC non-modular Surge Protection Device (SPD) is a high-quality, high-energy surge attenuation system that has been designed to protect sensitive equipment from damaging transient voltage surges. Proper installation is imperative to maximize the surge suppressor’s effectiveness and performance.
PACKAGING APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. · This equipment must only be installed and serviced by qualified electrical personnel. · Turn off all power supplying this equipment before working on or inside equipment. · Always use a properly rated voltage sensing device to confirm power is off.
APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) SAFETY LABELS LOCATION English versions of all safety labels (danger, warning, caution) are provided. SPD LOCATION CONSIDERATIONS Environment Audible Noise Mounting Service Clearance Equipment Performance The device is designed to operate in an ambient temperature range of -40 to +60 °C (-40 to +140 °F) with a relative humidity of 0 to 95% noncondensing. Refer to the product catalog for further details on enclosures.
ELECTRICAL APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) ELECTRICAL Voltage Rating Prior to mounting the SPD, verify that the device has the same voltage rating as the power distribution system in which it is installed by comparing the nameplate voltage or model number on the SPD with the nameplate of the electrical distribution equipment.
ELECTRICAL APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) WARNING UNDERSIZED WIRING (USE ONLY CONDUCTORS RATED 30 A OR GREATER.) · The brick panel series SPD is designed for connection to a 30 A (or greater) circuit breaker. · The circuit breaker is the intended disconnect means for the SPD without integral disconnect option and provides overcurrent protection for the connecting conductors. · The circuit breaker maximum rating should not exceed the ampacity of the connecting conductors.
ELECTRICAL SYSTEM GROUNDING APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) CAUTION SYSTEM GROUNDING · SPD must be installed on solidly grounded power systems. · Verify that the service entrance equipment is bonded to ground in accordance with all applicable codes. · Verify that the neutral terminals are grounded to system ground in accordance with all applicable codes. Failure to follow these instructions can result in equipment damage.
APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) INSTALLATION ELECTRICAL DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. · This equipment must only be installed and serviced by qualified electrical personnel. · Turn off all power supplying this equipment before working on or inside equipment. · Always use a properly rated voltage sensing device to confirm power is off.
INSTALLATION APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. · This equipment must only be installed and serviced by qualified electrical personnel. · Turn off all power supplying this equipment before working on or inside equipment. · Always use a properly rated voltage sensing device to confirm power is off.
WIRING APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) WIRING DIAGRAMS WITHOUT INTEGRAL DISCONNECT Figure 3: Single-Phase, 3-Wire, Grounded Chasis Ground Figure 4: Three-phase, 3- or 4-Wire, Grounded Wye Installation NOTE: The neutral conductor is not present on 3-wire, grounded neutral power systems. For these systems tie the neutral and ground lugs together.
OPERATION APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) OPERATION DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. · This equipment must only be installed and serviced by qualified electrical personnel. · Turn off all power supplying this equipment before working on or inside equipment. · Always use a properly rated voltage sensing device to confirm power is off.
OPERATION APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) AUDIBLE ALARM SURGE COUNTER Push the alarm enable/disable button to enable or disable the alarm. If the green alarm LED is lit the alarm is enabled. If the green alarm LED is not lit the alarm is disabled. The surge counter displays the number of transient voltage surges since the counter was last reset. The counter is battery powered to retain memory in the event of a power loss to the diagnostic display panel.
OPERATION APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. · This equipment must only be installed and serviced by qualified electrical personnel. · Turn off all power supplying this equipment before working on or inside equipment. · Always use a properly rated voltage sensing device to confirm power is off.
APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) MAINTENANCE AND TROUBLESHOOTING MAINTENANCE DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. · This equipment must only be installed and serviced by qualified electrical personnel. · Turn off all power supplying this equipment before working on or inside equipment.
TROUBLESHOOTING APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) Figure 5: Troubleshooting Flowcharts START Red phase LED(s) lit on Diagnostic Panel START YES Alarm on? NO Is alarm Enable/Disable LED on? Check communication connections.* Is Red LED(s) on? NO Check the voltage on each phase. Is the voltage correct? Check the power utility feed and verify voltage levels. Green phase LED(s) not lit. And, no Red LED(s) lit and no Alarm on.
APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) 19
CUSTOMER SUPPORT APC BRICK PANEL PRODUCTS Surge Protective Device (SPD) APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. – www.apc.