English versions of all safety labels (danger, warning, caution) are provided.
The device is designed to operate in an ambient temperature range of
-40 to +60 °C (-40 to +140 °F) with a relative humidity of 0 to 95% non-
condensing. Refer to the product catalog for further details on enclosures.
All SPDs operate normally without reduction in performance when
subjected to shock and vibrations described in IEC 60721-3-3, Class 3M4.
The device background noise is negligible and does not restrict the
location of the installation.
This device is designed to be surface or flush mounted. Refer to the device
submittal drawings or the product catalog for typical mounting dimensions
and weight. Install the Brick Panel SPD in a restricted access area.
The service clearance should meet all applicable code requirements.
To obtain the maximum system performance, locate the device as close
as possible to the circuit breaker to minimize the interconnecting wiring
length. For every foot in length of wire, approximately 175 volts per foot
(6 kV/ 3 kA, 8/20 microsecond) is added to the suppressed voltage.
The suppressed voltage rating is located on the device nameplate and
is measured 6 inches from the device terminals, according to UL
®
1449
Second Edition.
SAFETY LABELS
SPD LOCATION CONSIDERATIONS
Environment
Audible Noise
Mounting
Service Clearance
Equipment Performance