Install SPDs on the load side of the main overcurrent protection to comply
with UL 1449 and the NEC.
Locate the SPD as close as possible to the circuit breaker being protected
to minimize the wire length and optimize SPD performance. Avoid long wire
runs so that the device will perform as intended. To reduce the impedance
that the wire displays to surge currents, the phase, neutral, and ground
conductors must be routed within the same conduit and tightly bundled or
twisted together to optimize device performance. Avoid sharp bends in the
conductors. See Figure 2.
Figure 2: Wiring Practice
WARNING
UNDERSIZED WIRING
(USE ONLY CONDUCTORS RATED 30 A OR GREATER.)
· The brick panel series SPD is designed for connection to a 30 A (or greater) circuit breaker.
· The circuit breaker is the intended disconnect means for the SPD without integral disconnect
option and provides overcurrent protection for the connecting conductors.
· The circuit breaker maximum rating should not exceed the ampacity of the connecting conductors.
Failure to follow these instructions can result in death or serious injury.
LOCATION OF SPD
Phase A
Phase B
Phase C
Ground
Neutral
Interconnect wiring
- Minimize length
- Avoid sharp bends
Phases
Neutral
Ground
Neutral bus
Ground bus
To "protected" load(s)
APC BRICK PANEL PRODUCTS Surge Protective Device (SPD)
ELECTRICAL
Turn off all power supplying this equipment through the panel circuit breaker
before working on or inside the equipment.