Installation and Operation Manual 5
Proper installation is imperative to maximize the effectiveness and
performance of the Surge Protective Device (SPD). The installer should
follow the steps outlined in this instruction bulletin to ensure proper
installation. Read the entire instruction bulletin before beginning the
installation. These instructions are not intended to replace national or local
electrical codes. Check all applicable electrical codes to verify compliance.
Installation of surge suppressors should only be performed by qualified
electrical personnel.
Table 1:
SPD Device Per Phase I
2
tI
apparent
I
p
I
th
PM2X Series 44 kA
2
seconds 8,500 A RMS 20,000 A RMS 110 A
CAUTION
LOSS OF SURGE SUPPRESSION
During installation into an electrical system, SPDs must not be ener-
gized until the electrical system is completely installed, inspected, and
tested. All conductors must be connected and functional, including the
neutral. The voltage rating of the device and system must always be
verified before energizing the surge protective device.
Any factory or on-site testing of power distribution equipment that ex-
ceeds the normal operating voltage, such as high potential insulation
testing, or any other tests where the suppression components will be
subjected to voltages higher than their rated turn-on voltage must be
performed with the suppressor disconnected from the power source.
The neutral connection at the SPD device must also be disconnected
prior to performing high-potential testing and then reconnected upon
completion of the test.
Failure to follow these instructions can result in injury or equipment
damage.
NOTE: Type 2 SPDs are designed for use on
the load side of the service entrance Overcur-
rent Protection Device (OCPD) only.
NOTE: For troubleshooting, call APC Technical
Support at 1-800-800-4272.
Precautions