User Manual
Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower / Rack-Mount 2U 11
Installation
For UPS installation information, refer to the Installation Guide included with the UPS.
The Installation Guide is also available on the Documentation CD included with the UPS and on the APC by 
Schneider Electric Web site, www.apc.com.
Placement
The UPS is intended for IT environments. Avoid placement where there is excessive dust, temperature and 
humidity. Note that temperature in excess of 25
o
 C may have an adverse effect on battery and UPS life. All vents on 
the side or rear of the UPS should be free of obstructions. 
The UPS is heavy. For rack-mount units it is suggested that the batteries be removed for easier installation. The 
UPS should be placed near the bottom of the rack.
Connect to equipment and utilities
Note: The UPS will charge to 90% capacity in the first three hours of normal operation. 
Do not expect full battery runtime capability during this initial charge period.
1. Connect equipment to the outlets in 
the rear of the UPS. Some models are 
equipped with controlled outlet 
groups. Refer to the “Configuration” 
section of this manual for further 
instructions on the use of controlled 
outlet groups.
2. Connect the APC™ SmartConnect 
port   to your nearest network
switch using the cable provided.
3. Connect the UPS input to AC power. 
Note: Once power is connected the
display will be active.
4. Press the main power button   
on the UPS display to turn on the UPS 
output. 
Note: The On-line LED  will
light green when the output is on.
5. When the UPS is powered on for the first time the LCD screen displays the Setup Wizard and asks a number of 
basic set-up questions. They can be answered simply by using the arrow  and enter 
 keys 
on the display.
6. Log onto www.smartconnect.apc.com or scan the QR code to launch the registration process. The website 
includes instructions to setup your online account, activate your warranty and begin managing your UPS 
remotely.
 CAUTION
RISK OF DAMAGE TO EQUIPMENT OR PERSONNEL
•  Adhere to all local and national electrical codes.
•  Wiring should be performed by qualified electrician.
•  Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in injury.
LINK/A CT
NETWORK
su0968a