Overview The APC® by Schneider Electric service bypass panel (SBP), provides utility power to connected equipment during UPS maintenance. Inventory Read the Safety Guide before installing the SBP. Inspect the SBP upon receipt. Notify the carrier and dealer if there is damage. The package is recyclable; save it for reuse or dispose of it properly.
Specifications Electrical Specifications SKU SBP1500RM Voltage 120 VAC Amps 15 A SBP1500RMI 230 VAC 10 A SBP2200RM 120 VAC 20 A SBP3000RM 120 VAC 30 A SBP3000RMI 230 VAC 16 A SBP3000RMHW 208/220/230/240 VAC 16 A Environmental Specifications Temperature Maximum Elevation Humidity 2 Operating 0° to 40° C (32° to 104° F) Storage -15° to 45° C (5° to 113° F) Operating 3,000 m (10,000 ft) Storage 15,000 m (50,000 ft) This unit is intended for indoor use only.
Front Panels Callout Description Equipment outlets Bypass/UPS switch UPS output power cord Utility power cord UPS input power receptacle UPS output power receptacle Utility power receptacle Utility input terminal block access panel and hardwire knockout Equipment output terminal block access panel and hardwire knockout Equipment outlet circuit breaker SBP1500RMI SBP3000RMI Service Bypass Panel 1500/2200/3000 Rack-Mount Series User Manual su0589a SBP3000RMHW su0
Installation Changes and modifications to this unit not expressly approved by APC could void the warranty. Wall-Mount Options su0543a su0540a su0542a Use the rack-mount brackets for both wall and rack installations. Rack-Mount Options For horizontal installations use two screws and two cage nuts with each bracket on the SBP. su0516a For vertical installations use one screw and one cage nut with each bracket on the SBP.
Hardwire the SBP Hardwiring must be performed by a qualified electrician. Adhere to all national and local electrical codes. SBP3000RMHW model 1. Switch the utility circuit breaker off. 2. Remove the two screws that secure each access panel to the SBP. su0505a 3. Secure the utility power cables, Line1, Line2/Neutral, Ground to the input terminal block. Apply torque of 0.8 Nm (7 lb-in). 4. Secure the equipment power cables, Line1, Line2/Neutral, Ground to the output terminal block. Apply torque of 0.
Operation Bypass mode SBP bypass mode enables connected equipment to operate on utility power while UPS maintenance is performed. Note: Connected equipment is not protected by the UPS while the SBP is in bypass mode. UPS mode While the SBP operates in UPS mode, power is supplied to connected equipment from the UPS and is protected from power variations and disturbances. Troubleshooting Use the table to solve minor installation and operation problems. Refer to the APC Web site, www.apc.
Service If the unit requires service, do not return it to the dealer. Follow these steps: 1. Review the Troubleshooting section of the manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com. a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the top of the unit. b. Call APC Customer Support and a technician will attempt to solve the problem over the phone.
Contact information APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/ Global support searching APC Knowledge Base and using e-support.
OUT OF, APC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC WARRANTIES EXTEND ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.