Installation guide
27Installation Guide Silcon DP300E Series 480V 120-160kVA
7OH0006 US rev. 03
Connection
4.4 SmartSlot for Silcon DP3120E – DP3160E
A UPS system alone provides excellent protection from brief power problems. How-
ever, during an extended power outage an unattended computer system will eventu-
ally shut down due to battery capacity exhaustion. To prevent data corruption when
the UPS shuts down, the computer must be informed by the UPS of impending shut
down and take appropriate file-saving measures. This important function is called
UPS monitoring. The UPS’s computer interface port is the means by which your UPS
communicates with a computer system.
Some computer operating systems have built-in UPS monitoring. These systems
require various hardware interfaces. Interface kits for all major operating systems
that support UPS monitoring are available from your dealer.
APC SmartSlot for Silcon DP300E Series UPS’s has been designed for reliable and
maintenance-free service in combination with your American Power Conversion
(APC) Silcon DP300E Series uninterruptible power supply (UPS).
4.4.1 SmartSlot Accessories
SmartSlot at the front of the frame accomodate up to 3 accessory cards. Before in-
stalling any SmartSlot accessory, ensure it is a compatible “Silcon DP300E OK”
model.
1. Share-UPS TM, provides automatic shutdown of up to two additional servers.
2. Measure-UPS TM II, provides environmental information such as ambient
temperature and humidity.
3. Call-UPS TM, works with an external modem to provide out-of-band UPS
manegement
4. WEB/SNMP Management card, provides web based UPS management.
4.4.2 Multiple SmartSlot Installation - introduction
If your UPS configuration uses more than one SmartSlot device, you must install
them in the correct order for them to work together properly.
Priority of SmartSlot devices:
A SmartSlot device with higher priority is to be placed in the SmartSlort accessory
slot with the higher number. Refer to the following table.
Priority of APC accessories:
Install SmartSlot accessories as dictated by the following table. An accessory with
higher priority is to be placed in the accessory slot with the higher number.
Accessory P/N Priority Position
Web/SNMP AP9606S Highest High–numbered slot
Management Card
Call-UPS ® // AP9608 Second-highest
Interface expander AP9607 Second–lowest
Measure-UPS ® // AP9612T Lowest
AP9612TH Low–numbered slot