Installation guide

30 Installation Guide Silcon DP300E 480V 120-160kVA
7OH0006 US rev. 03
Connection
Utility 2 Output
Q3
Trip function
Q10
Trip function
Q1
Trip function
Utility 1
UPS
Q2
Trip function
EPO
X001
EPO SW
Trip function
Ext. batt.
cubicle or
batt. room
All MCCB’s in ext. batt.
cubicle or batt. room must
be provided with trip
function
Used for
tripping all
switches in
switch gear
and batt.
MCCB’s
All switches in switch gear must
be provided with trip function
User supplied electronics
and supply for tripping of
MCCB’s and switches
The other part of the EPO switch has interconnection to an electronic control system
(not supplied by APC), supplying the tripping function in the MCCB and switchgear
with an external 277Vac or 480Vac 50/60Hz supply, supported from Utility 2, if
available, or Utility 1 and from the output of the UPS before Q002.
This combination of 2 break function, one for the UPS system and one for external
switchgear makes it possible to make a quick shutdown of the total system in case of
emergency.