61Installation Guide Silcon DP300E Series 480V 120-160kVA
7OH0006 US rev. 03
Options/Accessories
5.5.1 Mounting seismic anchoring
16 holes for Ø10mm bolts have to be drilled according to dimensioned sketch, where
the UPS system is to be placed.
The system is placed after drilling the holes, then 8 angles for seismic anchoring are
to be fitted into the bars, see above. The angles are then tightened in the holes.
The angles for seismic anchoring are placed as shown above and bolted with bolts
and plain washer.
8 seismic anchoring angles
IMPORTANT:
Remember to tighten all bolts in
the 8 angles to the floor. Bolts
for the floor are not enclosed.