Installation guide
66 Installation Guide Silcon DP300E 480V 120-160kVA
7OH0006 US rev. 03
5.7.2.3 Cables for remote display
RS232C to RS232C cable:
Connect shield at one end only!
Rating: Please refer to Local/National electrical codes for more
information,communication voltage ±15V
DC
DP300E, DB25S Remote Display, DB9P
2 TxD
3 RxD
7 GND
3 TxD
2 RxD
5 GND
Options/Accessories
5.7.2.2 Remote display power supply
The remote display power supply is a normal AC power supply with no battery back-
up. This means that if data transmission with the Silcon DP300E has to continue
during break down of the commercial utility, the remote display has to be supplied
from the Silcon DP300E or another uninterruptible power source.