7Installation Guide Silcon DP300E Series 480V 120-160kVA
7OH0006 US rev. 03
Placing
3.0 Placing
3.1 Requirements on the Installation Site
The system is designed with parts accessible from front or top and cable entries from
top or bottom.
The system can be placed close to walls, only free space for front door opening has to
be ensured.
Sufficient cooling and service clearance must be ensured by a free space of min. 3
feet above and in front of the system.
Avoid placing the system in direct sunlight.
3.2 Dimensions and Weights
3.2.1 Dimensions and Weights Silcon DP3120E–DP3160E
Type Height Width Depth Weight
inch/mm inch/mm inch/mm lbs/kg
DP3120E/480V 70.86/1800 67.00/1600 31.50/800 2643/1200
DP3160E/480V 70.86/1800 67.00/1600 31.50/800 2643/1200
Cubicle
67.00 / 1600 in./mm wide
70.86 / 1800 in./mm
WARNING!
Do not stand on or place any
object on any UPS cabinet or
UPS cubicle due to personal
and product safety.