Operation Manual Smart-UPS® UPS 750/1000/1500/2200/3000 VA Tower 120/230 VAC
Contents Overview .......................................................................... 1 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Front panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 EPO Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Normally open contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Normally closed contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Troubleshooting ............................................................ 12 Service and Support.............................
Overview Product Description The APC® by Schneider Electric Smart-UPS® 750-3000 VA 120/230 Vac Tower is a high performance Uninterruptible Power Supply (UPS). It provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges; small utility fluctuations and large disturbances. The UPS also provides battery backup power until utility power returns to safe levels or the batteries are fully discharged.
Rear panels USB port 750 VA 120 Vac 750 VA 230 Vac Serial port Ground screw Smart slot Circuit breaker UPS input su0326a EPO connector su0327a Outlets 1000/1500 VA 120 Vac 1000/1500 VA 230 Vac su0325b su0328b GR O U P 1 GR O U P 1 2200 VA 120 Vac/3000 VA 120 Vac† 2200/3000 VA 230 Vac GROUP 1 su0351b su0329b G R OU P 1 †Circuit breaker may be different than shown.
Specifications Operating Conditions This unit is intended for indoor use only. Select a location sturdy enough to support the weight of the UPS. Do not operate the unit where there is excessive dust, or the temperature or humidity are outside the specified limits. This unit has side air vents. Allow adequate space for proper ventilation. Environmental Specifications Environmental factors impact battery life.
Operation Connect Equipment to the UPS Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery run capability during this initial charge period. 1. Connect equipment to the outlets on the rear panel of the UPS. Do not use extension cords, plug equipment directly into the UPS. 2. Connect the UPS to the building utility power. Connect the UPS to a two-pole, three-wire, grounded receptacle only. 3.
Display Interface Overview Online indicator UPS Output On/Off button On Battery indicator Fault indicator Replace Battery indicator Display screen UP/DOWN buttons ENTER button ESCAPE button APC by Schneider Electric su0343a Using the display interface Use UP and DOWN to scroll through the main menu options. Press ENTER to view the sub-menus under each main menu option. Press ESCAPE to exit a sub-menu and return to a main menu.
Menu General Functions About Display information about this unit: • Unit model number • Serial number • Battery installation date • Suggested battery replacement date • Replacement Battery Cartridge model number • UPS firmware version Advanced menus The Advanced menus provide additional options for the UPS and are available only if the display interface is configured to use the Advanced menus.
Configuration UPS Settings Start-up Settings Configure these settings at initial start-up, using the display interface or APC PowerChute® software. Note: During start-up, use the display interface to configure these settings. If nothing is selected, the until will use the default settings. Function Factory Default Options Description Language English • English • French* • German* • Spanish* • Italian* The language for the display interface.
Function Factory Default Options Low Transfer Point 120 V: 106 Vac • 97 Vac • 100 Vac • 103 Vac • 106 Vac 230 V: 208 Vac • 196 Vac • 200 Vac • 204 Vac • 208 Vac Nominal Output 120 Vac Voltage 230 Vac N/A Transfer Sensitivity High, Low, Medium High 208-252 Vac Description Set the transfer point lower if the utility voltage is chronically low and the connected equipment can tolerate this condition.This setting may also be adjusted using the power quality setting.
Main Outlet Group and the Switched Outlet Group Overview The Main Outlet Group and the Switched Outlet Group can be configured to independently turn off, turn on, shut down, and reboot connected equipment. (These features are not available on the 750 VA units.
Function Factory Default Options Name String Outlet Group Outlet Group 1 UPS Name String UPS Outlets Description Edit these names using an external interface, such as the Network Management Card Web interface. Turn On Delay 0 sec Set the value in seconds The amount of time the UPS or Switched Outlet Group will wait between receiving the command to turn on and the actual startup.
Emergency Power Off EPO Overview The Emergency Power Off (EPO) option is a safety feature that will immediately disconnect all connected equipment from utility power. The UPS will immediately shut down and will not switch to battery power. The UPS must be manually re-started to re-apply power to connected equipment and to the UPS. Press ON/OFF on the front panel of the unit. 1.
Troubleshooting Problem and Possible Cause Solution The UPS will not turn on or there is no output The unit has not been turned on. Press the ON button once to turn on the UPS. The UPS is not connected to utility power. Ensure that the power cable is securely connected to the unit and to the utility power supply. The input circuit breaker has tripped. Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker. The unit shows very low or no input utility voltage.
Problem and Possible Cause Solution The replace battery indicator is illuminated The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a self-test. If the problem persists after recharging, replace the battery. The replacement battery is not properly connected. Ensure that the battery connector is securely connected.
Service and Support Service If the unit requires service, do not return it to the dealer. Follow these steps: 1. Review the Troubleshooting section of the UPS manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com. a. Note the model number and serial number, located on the rear of the unit, and the date of purchase. b. Call APC Customer Support and a technician will attempt to solve the problem over the phone.
Transport the unit 1. Shut down and disconnect all connected equipment. 2. Disconnect the unit from utility power. 3. Disconnect all internal and external batteries (if applicable). 4. Follow the shipping instructions outlined in the Service. APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.
Smart-UPS Factory Warranty LIMITED WARRANTY American Power Conversion (APC) warrants its Smart-UPS (Products) to be free from defects in materials and workmanship for a period of three (3) years, excluding the batteries, which are warranted for two (2) years from date of purchase. APC's obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products.
EC Declaration of Conformity 2009 Date of product declaration Harmonized Standards EN62040-1-1, EN62040-2, EN60950-1, IEC60950-1, EN55022, EN55024, IEC61000-3-2, 3-3, 4-2, 4-3, 4-4, 4-5, 4-6, 4-11 Applicable Council Directives 2006/95/EC; 2004/108/EC Type of Equipment Uninterruptible Power Supply Model Numbers SMT750I, SMT1000I, SMT1500I, SMT2200I, SMT3000I Manufacturers American Power Conversion 132 Fairgrounds Rd West Kingston, RI 02892 USA American Power Conversion 2nd Street, PEZA Cavite Econ
© 2009 APC by Schneider Electric. APC, the APC logo are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.