User's Manual

Smart-UPS C 1000/1500 VA 120/230 Vac Tower / Rack-Mount 2U 7
Installation
For UPS installation information, refer to the Installation Guide included with the UPS.
The Installation Guide is also available on the Documentation CD included with the UPS and on the APC by
Schneider Electric Web site, www.apc.com.
Placement
The UPS is intended for IT environments. Avoid placement where there is excessive dust, temperature and
humidity. Note that temperature in excess 25
o
C may have an adverse effect on battery and UPS life. All vents on
the side or rear of the UPS should be free of obstructions.
The UPS is heavy. For rack-mount units it is suggested that the batteries be removed to facilitate easier installation.
The UPS should be placed near the bottom of the rack.
Connect to equipment and utilities
Note: The UPS will charge to 90% capacity in the first three hours of normal operation.
Do not expect full battery runtime capability during this initial charge period.
Model Dimensions (in/mm) H x W x D Weight (lb / kg)
SMC1000C, SMC1000IC
8.6 x 6.7 x 17.3 in (219 x 171 x 439 mm)
37.5 / 17
SMC1500C, SMC1500IC 44.3 / 20.1
SMC1000-2UC, SMC1000I-2UC 3.4 x 17 x 16 in (86 x 432 x 409 mm) 39.3 / 17.8
SMC1500-2UC, SMC1500I-2UC 3.4 x 17 x 18.8 in (86 x 432 x 477 mm) 55.8 / 25.3
CAUTION
RISK OF DAMAGE TO EQUIPMENT OR PERSONNEL
Adhere to all local and national electrical codes.
Wiring should be performed by qualified electrician.
Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in injury.