Operation Manual Smart-UPS™ C Uninterruptible Power Supply 1000/1500/2000/3000 VA 120/230 Vac Rack-Mount 2U su00 812a
Important Safety Messages SAVE THESE INSTUCTIONS - This manuals contains important instructions that should be followed during installation and maintenance of the Power Management Unit, Service Bypass Unit and batteries. Read the instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it.
• Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity. • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. • The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment. Battery safety • It is not necessary to ground the battery system.
Product Description The APC™ by Schneider Electric Smart-UPS™ C is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from AC power blackouts, brownouts, sags, and surges, small AC power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until AC power returns to acceptable levels or the batteries are completely discharged.
Product Overview Front panel features 1000VA 120/230 Vac Display interface Bezel su05 63 c Battery Internal battery connector 1500 VA 120/230 Vac 2000 VA 230 Vac 3000 VA 230 Vac su093 6a 4 Smart-UPS C 1000/1500/2000/3000 VA 120/230 Vac Rack-Mount 2U su0 6 30c
Rear panel features UPS input Circuit breaker/Overload protection Chassis ground screw Outlets USB port Serial data port 1000 VA 230 Vac 1500 VA 120 Vac su0644d su0644c 1000 VA 120 Vac UPS input Circuit breaker/Overload protection Chassis ground screw Outlets USB port Serial data port 2000 VA 230 Vac su0644f su0644e su0644b 1500 VA 230 Vac su0644g 3000 VA 230 Vac Installation For UPS installation information, refer to the Installation Guide for the Smart-UPS C 1000/150
Operation Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period. 1. Connect equipment to the UPS. 2. Connect the UPS to a two pole, three wire, grounded source. CAUTION RISK OF ELECTRIC SHOCK • Adhere to all local and national electrical codes. • Wiring must be performed by qualified electrician. su0628b • Always connect the UPS to a grounded outlet.
Sensitivity adjustment settings The UPS detects and reacts to line voltage distortions by transferring to battery backup power to protect connected equipment. In situations where the connected equipment is too sensitive for the input voltage level it is necessary to adjust the transfer voltage. 1. Connect the UPS to a AC power source. Be sure the UPS is turned off. 2. Place the unit in Configuration Mode, as described in page 10. 3. Use the Sensitivity Setting option to set the transfer voltage range.
LED status indicators Status Audible Indicator On LED Audible Indicator Terminates Power On The UPS is supplying AC power to connected equipment. The On Line/On None Battery LED illuminates green. On Battery The UPS is supplying battery power from the internal battery. The On Line/On The UPS beeps The beeping stops when AC power is Battery LED 4 times every restored or the MUTE button is pressed for two seconds. illuminates amber. 30 seconds.
Display icons 120 Vac 230 Vac Description On Line: The UPS is supplying conditioned AC power to connected equipment. Green mode: The UPS is operating at the most efficient level, bypassing unused AVR components while acceptable AC voltage is present. The UPS will enter and exit Green mode automatically and will not compromise power protection. Load Capacity: The load capacity percentage is indicated by the number of load bar sections illuminated. Each bar represents 20% of the load capacity.
On Battery: The UPS is supplying battery backup power to the connected equipment. System Alerts P00 Output Overload 120 Vac 230 Vac P01 Output Short Circuit P02 Output Over Voltage su0752a su0752b P04 Unit Over Temperature P06 AVR Relay Alert P13 Inverter Alert For more information on System Alerts, contact customer support at the APC by Schneider Electric web site, www.apc.com/support. Feature Reference Guide Normal Mode Timing (seconds) UPS State Power On 0.
Function Self-Test Options Description • 0: Default Setting When set to 1, pressing the DISPLAY button will trigger the self test • 1: Begin Self-Test and exit the Configuration Mode. 0 is the default setting and will not initiate a self test, by pressing the DISPLAY button you will advance to the next configuration item. Note: When the UPS is in Configuration mode and the UPS output power is off, a Self-Test cannot be initiated.
Troubleshooting Problem and Possible Cause Solution The UPS will not turn on or there is no output The UPS has not been turned on. Press the ON button once to turn on the UPS. The UPS is not connected to AC power. Be sure the power cable is securely connected to the UPS and to the AC power supply. The input circuit breaker has tripped. Disconnect nonessential equipment and reset the circuit breaker.
Battery Replacement Always recycle used batteries. For information on recycling a used battery, refer to the Battery Disposal Information sheet included with the replacement battery. Battery life is highly dependent on temperature and use. To identify when to replace batteries, SmartUPS have a predictive battery replacement date indicator in the “About” menu and automatic (and configurable) self-tests. Proactively replace batteries to maintain the highest availability.
Transport 1. Shut down and disconnect all connected equipment. 2. Disconnect the unit from utility power. 3. Disconnect all internal and external batteries (if applicable). 4. Follow the shipping instructions outlined in the Service section of this manual. Service If the unit requires service, do not return it to the dealer. Follow these steps: 1. Review the Troubleshooting section of the manual to eliminate common problems. 2.
Two Year Limited Factory Warranty Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship for a period of two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or parts thereof does not extend the original warranty period.
16 Smart-UPS C 1000/1500/2000/3000 VA 120/230 Vac Rack-Mount 2U
APC by Schneider Electric Worldwide Customer Support Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways: • Visit the APC by Schneider Electric Web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC by Schneider Electric Web sites for specific countries, each of which provides customer support information.