Specifications
SURT15k/20k 230 VAC Stack/Rack-Mount 6U XLI/XLICH/XLI-CC24
Threshold
Alarm
Load Power Is Above
Alarm Limit.
The load has exceeded the user- specified
load alarm threshold.
Option 1) Use the display interface to
raise the alarm threshold.
Option 2) Reduce the load
Load Is No Longer Above
Alarm Threshold.
The load exceeded the alarm threshold.
The situation has been corrected. Either
because the load decreased or the
threshold was increased.
No corrective action is necessary.
Min Runtime Restored. The system runtime dropped below the
configured minimum and has been
restored:
1) Additional battery modules were
installed.
2) The existing battery modules were
recharged.
3) The load was reduced.
4) The user- specified threshold was
decreased.
General Fault Need Bat Replacement. One or more battery pairs are in need of
replacement.
Refer to battery installation procedure.
No Batteries Are
Connected.
No battery power is available. Check that batteries are installed and
connected properly.
Discharged Battery. The UPS is on battery operation and the
battery charge is low.
Shut down the system and the load or
restore the incoming voltage.
Low- Battery. The UPS is on battery operation and the
battery charge is low.
Weak Batt(s) Detected.
Reduced Runtime.
One or more weak battery pairs detected
(only applicable for internal battery
modules).
Replace the weak battery pairs.
Batt Temperature Exceeded
Upper Limit.
The temperature of one or more battery
packs has exceeded system
specifications.
Contact APC Customer Support. Refer
to Contact Information in this manual.
Battery Over-Voltage
Warning.
The battery voltage is too high and the
charger has been deactivated.
Runtime Is Below Alarm
Threshold.
The predicted runtime is lower than the
user-specified minimum runtime alarm
threshold. Either the battery capacity has
decreased, or the load has increased.
Option 1) Allow the batteries to
recharge.
Option 2) If possible, increase the
number of battery modules.
Option 3) Reduce the load.
Option 4) Decrease the alarm threshold.
Shutdown Due To Low
Battery.
The UPS shutdown while on battery
operation.
No corrective action is necessary.
Note: Should this situation reoccur,
consider increasing battery capacity.
Bypass Not Available Input
Freq/Volt out Of Range.
The frequency or voltage is out of
acceptable range for bypass. This
message occurs when the UPS is online.
Correct the input voltage to acceptable
frequency or voltage.
Mains Not Available. Input
Frq/Volt Out of Range.
The frequency or voltage is out of
acceptable range for normal operation.
Emergency PSU Fault. Redundant Emergency Power Supply
Unit (PSU) is not working. Internal
diagnostic fault. The UPS will continue to
operate normally.
Contact APC Customer Support. Refer
to Contact Information in this manual.
Condition
PowerView Display
Message Reason for Message Corrective Action