Datasheet
Written by Paul
Ayers
SURT1000XLIM with filter SURT023M*
SURT6000XLIM with filter SURT024M*
Technical Specification
SURT1000XLIM
SURTD2200XLIM
SURTD3000XLIM
SURT6000XLIM
OPERATION
Power Capacity
1000VA (700W)
2200VA (1540W)
3000VA (2100W)
6000VA (4200W)
Input Voltage (default 230V)
208, 220, 230, 240V
Input Voltage Range (Full Load, t = 40°C )
160V to 280V
Input Voltage Range (Half Load, t = 40°C)
100V to 280V
Input Voltage Range (Full Load, t= 55°C)
180V to 280V
Input Voltage Range (Half Load, t= 55°C)
112.5V to 280V
Input Frequency Range
45Hz – 65Hz
Input Connection
IEC 320 C14
IEC 320 C20
IEC 320 C20
Hardwire (H, N,G)
Output Voltage (default 230V)
208, 220, 230, 240V
Output Voltage Regulation
+/-1%
Output Frequency
Default: 50/60+/-3Hz autotracking, or fixed 50Hz or 60Hz +/- 0.1Hz
Efficiency
88%
90%
91%
92%
Output Connections
(6) IEC 320 C13
(8) IEC 320 C13, (2) IEC 320 C19
BATTERIES & RUNTIME
Runtime at Full Load
7 min
21 min
14 min
5 min
Runtime with (1) External Battery Pack
47 min
80 min
57 min
21 min
Runtime with (2) External Battery Pack
87 min
144 min
103 min
40 min
External Battery Pack Part Number
SURT48RMXLBP
SURT192RMXLBP
Maximum Number of Battery Packs
unlimited
CONNECTIVITY
Emergency Power Off
NO
YES
Manual bypass switch
NO
YES
Relay I/O
Serial port signaling and optional Relay I/O Card AP9613
Communication Port
DB9 Serial
RJ-50 Serial
RJ-50 Serial
DB9 Serial
Networking (SNMP, Ethernet, etc.)
Optional Network Management Card AP9630 or AP9631 (AP9631 also provides Relay I/O)
PHYSICAL
Rack Height
2U
3U
Dimensions (mm) H x W x D
432 x 85 x 483
432 x 130 x 660
Weight (Kg)
23
54.5
Marine Filter * Part Number
SURT023M
SURT024M
* Marine Filter Required for DNV Compliance in applications that require DNV EMC Class B (e.g. the bridge)
DNV Type Approved
UPS for Marine Applications