Installation and Operation Smart-UPS® Uninterruptible Power Supply Tower/Rack-Mount 2U SURTA 1500XL/1500RMXL2U/1500XLJ 2200XL/2200RMXL2U su0541a 100/120 Vac
This manual and the safety guide are available in English on the enclosed CD and the APC Web site, www.apc.com. Este manual y la guía de seguridad están disponibles en español en el CD adjunto y en el sitio Web de APC, www.apc.com. Ce manuel et le guide de sécurité sont disponibles en français sur le CD-ROM ci-inclus et sur le site Web d'APC, www.apc.com. 本書及び安全ガイドの日本語版は、同梱の CD 及び APC の Web サイト(www.apc.com)からご覧戴けます。 ⎥ ↵ ⊗ ⊃™ ®× © ⎛⊄ ÷ ⏐∝ ⊗ ΧΔ ⎣© ΑΠΧ ⎠⊆ ∏ ⎯≤ ♦ ωωω.απχ.
Smart-UPS® Uninterruptible Power Supply Tower/Rack-Mount 2U SURTA1500XL/1500RMXL2U/1500XLJ SURTA2200XL/2200RMXL2U 100/120 Vac English
Overview The APC® by Schneider Electric Smart-UPS® SURTA1500XL/2200XL is a high performance uninterruptible power supply (UPS). It provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges; small utility fluctuations and large disturbances. The UPS also provides battery backup power until utility power returns to safe levels or the batteries are fully discharged.
Product Overview Front display panel Load Battery Charge Test su0311b Button or Indicator Description The ON button: has three functions. Press this button to turn on the UPS. Press this button to initiate a Cold Start. Cold Start is not a normal condition. When there is no utility power and UPS is off, press and hold this button to restore power to UPS. UPS will emit two beeps. During second beep, release the button. Press this button to initiate a Self-Test.
Front Display Panel Feature Description The UPS has a diagnostic feature that indicates utility voltage. 100V 118.0 108.7 99.3 90.0 80.6 120V 138.2 128.8 119.5 110.1 100.8 The UPS starts a self-test as part of this procedure. The self-test does not affect voltage display. Press and hold the ON button to view utility voltage bar graph indicator.
Specifications Temperature Maximum Elevation Humidity This unit is intended for indoor use only. Select a location sturdy enough to handle the weight. Operating 0° to 40° C (32° to 104° F) Storage -15° to 45° C (5° to 113° F) charge UPS battery every six months Operating 3,000 m (10,000 ft) Do not operate UPS where there is excessive dust or temperature or humidity are outside specified limits. Storage 15,000 m (50,000 ft) This unit has side air vents.
Operation Connect equipment to the UPS 1. Connect equipment to UPS. Do not use extension cords, plug equipment directly into the UPS outlets. 2. If applicable, connect equipment to the serial or USB ports. 3. Add optional accessories to the SmartSlot. 4. For additional system security, install PowerChute software. Refer to the PowerChute Utility CD for instructions. 5. External battery packs provide extended runtime during power outages. Refer to the APC Web site, www.apc.
Configuration UPS Settings Configure the settings using PowerChute software, a network management card or terminal mode. Function Factory Default Options • On startup and every 7 days (168 hours) there after • On startup and every 14 days (336 hours) there after • On startup only • No self-test Description Set the interval at which the UPS will execute self-tests.
Function Factory Default Low Bypass Points 100 Vac models 78 Vac 120 Vac models 86 Vac Output Frequency Options • • • • 78 Vac 80 Vac 82 Vac 84 Vac • • • • 86 Vac 88 Vac 90 Vac 92 Vac • • • • 86 Vac 88 Vac 90 Vac 92 Vac • • • • 94 Vac 96 Vac 98 Vac 100 Vac Automatic selection between: Automatic 50 ± 3 Hz 50 ± 3Hz 60 ± 3 Hz 60 ± 0.1 Hz 50 ± 0.1 Hz Description Minimum voltage that the UPS will pass to connected equipment during internal bypass operation. Specify the UPS output frequency.
TERMINAL MODE TO CONFIGURE UPS PARAMETERS Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wishing to use PowerChute® software or an optional Network Management Card. Connect the serial cable to the serial com connector on the back of the UPS. If PowerChute software is not installed do not perform steps 1, 2, 8 and 9. 1.
Troubleshooting Problem and Possible Cause Solution The UPS will not turn on or there is no output The unit has not been turned on. Press the ON button once to turn on the UPS. The UPS is not connected to utility power. Ensure that the power cable is securely connected to the utility power supply. The input circuit breaker has tripped. Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker. The unit shows very low or no input utility voltage.
Problem and Possible Cause Solution All indicators flash sequentially The UPS has been shut down remotely None. The UPS will restart automatically when utility power returns. through software or an optional accessory card. All indicators are illuminated and the UPS emits a constant beeping sound The UPS detects an internal fault. Do not attempt to use the UPS. Disconnect the UPS from utility and battery power. Have the UPS serviced immediately.
Problem and Possible Cause Solution Fault and Overload indicators are illuminated and the UPS emits a sustained alarm tone The UPS is not sending power to connected equipment. Connected equipment exceeds specified “maximum load” as defined in Specifications on APC Web site, www.apc.com. The alarm remains on until the overload is removed. Disconnect nonessential equipment from UPS to eliminate overload condition. The UPS will not provide power from batteries in the event of a utility voltage interruption.
Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in “Troubleshooting” on page 10 in this manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com. a. Note the model number of the UPS, the serial number located on the rear side of the unit, and the date purchased.
Limited Warranty Two-Year Warranty The limited warranty provided by American Power Conversion (APC®) in this statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your business. Terms of warranty APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase.
Radio Frequency Warning 120 Vac models This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. This equipment has also been tested and found to comply with the limits for a Class B digital device. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment for Class A and a residential environment for Class B.
990-3622 7/2009