Specifications

Cables
RecommendedCableSizes
Note:
RefertoIEC60364-5-52forinstallationmethods.TherecommendedcablesizesareforinstallationmethodB2andbasedonanenvironmentwithan
ambienttemperatureof30°C.
Note:
Temperatureratingsofconductors:70°C.UseonlycopperconductorsandPVCisolatedcables.
380V,400V,and415V
10kV A15kV A20kV A30kV A40kV A
Utility/mainsinput(mm
2
)
2.56101625
Staticbypassinput(mm
2
)
2.56101625
DCinput(mm
2
)
5050505050
Output(mm
2
)
2.56101625
TorqueSpecications
Thepowerwiringshouldbetorquedto7Nm.
Smart—UPSVT10–40kVA380/400/415VQuickReference
23