Specifications
Q3andQ4inParallelCapacitySystems
Unitsinparallel10kV A15kV A20kV A30kV A40kV A
2(A)
355063100125
3(A)
5080100160200
4(A)
63100200200250
Q3andQ4inParallelRedundantSystems(n+1)
Unitsinparallel10kV A15kV A20kV A30kV A40kV A
2(A)
1625355063
3(A)
355063100125
4(A)
5080100160200
MinimumBreakerSettings
800%overloadbypass
operation
150%overload
normal/batteryoperation
125%overload
normal/batteryoperation
Continuously
Duration
500ms60s
10min
Mainsinput
-
1
--
16.4A
Staticbypassinput
121.5A
--
16.7A
10kV A
UPSoutput121.5A22.8A19A16.7A
Mainsinput
-
1
--
24.6A
Staticbypassinput
182A
--
25.1A
15kV A
UPSoutput182A34.2A25.4A25.1A
Mainsinput
-
1
--
32.5A
Staticbypassinput
244A
--
33.4A
20kV A
UPSoutput244A45.6A38A33.4A
Mainsinput
-
1
--
49.1A
Staticbypassinput
364A
--
50.1A
30kV A
UPSoutput364A68.4A57A50.1A
Mainsinput
-
1
--
65.6A
Staticbypassinput
487A
--
66.9A
40kV A
UPSoutput487A91.2A76A66.9A
1
Forsinglemainssystems,usethehighervalueofmainsandstaticbypass
Smart—UPSVT10–40kVA380/400/415VQuickReference
27