Specifications
CommunicationandManagement
NetworkManagementCard
Thesystemisequippedwithonenetworkmanagementcardforremotemonitoringandcontrolofanindividual
UPSbyconnectingitdirectlytothenetwork.
InputandOutputContacts
Pins7and8areforexternalchargecontrol.When7and8areclosed,theUPSchargesbatterieswithapre-dened
percentage(0-25-50-75-100%)ofthemaximumchargingpower.Tobeusedingeneratorapplications,orif
specialcodesrequirecontrolofcharging.WhenQ3isclosed,signalsarefedbacktotheUPScontroller.
Pins5and6areforexternalmaintenancebypassQ3(auxiliaryswitchN/Ctype).WhenQ3isclosed,signals
arefedbacktotheUPScontroller(seeQ3drawing).
Pins1to4areforbatterymeasurement(onlyapplicabletoAPCXRBatteryEnclosures-seeJ200drawing).
28
Smart—UPSVT10–40kVA380/400/415VQuickReference