Symmetra PX 250/500 kW 400/480 V Single and Parallel Operation
Table of Contents Overview .............................................................................................................................. 1 Symbols used ............................................................................................................... 3 Parallel System Summary.......................................................................................... 3 UPS Summary Screen ..............................................................................................
Set the Battery Test Settings ....................................................................................26 Set the Display Settings .............................................................................................28 Set the Network Management Card (NMC) Settings...........................................29 Set the User Password Settings ..............................................................................30 Set the Alarm Settings................................................
Overview Display Overview Note: The screens shown in this manuals are examples only. The UPS graphical user interface is located in the Input/Output/Bypass Enclosure. The UPS utilizes the touch-screen display to configure and monitor the system, and provides the user with visible and audible alarms. The screens are organized hierarchically. In parallel systems the Parallel System Summary screen is at the top of the hierarchy. In single systems the UPS Summary screen is at the top of the hierarchy.
Navigation Parallel System Summary Parallel Input Summary Parallel Bypass Summary Parallel Output Summary UPS System UPS Summary UPS Input Summary UPS Bypass Summary UPS Battery Summary System Status Subfeed Summary UPS Output Summary UPS System System Information System Status Event Log Firmware Overview Predictive Maintenance Configuration User Configuration Service Configuration Factory Configuration Operation Start-Up Shutdown Transfer to normal operation Transfer to static bypass Isolate this UPS Langu
Symbols used WARNING: Indicates an electrical hazard, which, if not avoided, could result in injury or death. Caution: Indicates a hazard, which, if not avoided, could result in injury or death. Note: Indicates important information. See: Indicates that more information is available on this subject. Parallel System Summary The Parallel System Summary screen is the home screen in parallel systems. It provides you with an overview of the parallel system and circuit breakers.
UPS Summary Screen Single System In single systems, the UPS Summary screen is the home screen. It provides you with an overview of the UPS system and circuit breakers. It shows the system status and the power flow through the system and gives access to the system’s summary screens and the UPS System screen. A. Access further details on the current screen. B. Go to the UPS System screen. C. Go to the System Status screen for the current UPS. D. Go to the Bypass Summary screens. E.
Operation Modes UPS Modes The UPS operation mode is indicated in the top right corner of the screen under the heading UPS Mode. The UPS mode indicates the current status of the operated UPS. Normal Operation During normal operation, the UPS supports the critical load with conditioned power. While the UPS is operating in normal operation, a single-line diagram will appear on the screen. A green line indicates the power flow from the utility/mains, through the UPS system, and to the load.
Battery operation If the utility/mains supply fails, the UPS transfers to battery operation. During battery operation, battery power ensures uninterrupted support to the critical load. While the UPS system is in battery operation, a single-line diagram will appear on the screen. The green line indicates the power flow from the batteries, through the inverters, and then to the load.
Requested static bypass operation/forced static bypass operation The UPS is in requested static bypass following a command from the graphical user interface. And the UPS is in forced bypass when a fault on the system has caused static bypass operation. During static bypass operation, the critical load is supplied directly by utility/mains power. While the UPS is operating in this mode, a single-line diagram will appear on the screen.
Battery test The UPS is in battery test mode when the UPS is performing a battery self-test. During battery test, the battery runtime capacity is reduced by 10%. Note: The battery test will stop if the mains supply fails during the test.
System Modes The system mode is indicated in the top right corner of the screen under the heading System Mode. The system mode indicates the current output status of the complete system, and not the individual UPS unit. On When the system mode is On, the UPS system supports the critical load with conditioned power. The load is supported by the UPS in both normal and battery operation. Off When the system mode is Off, the UPS system does not support the connected load with power.
Maintenance bypass operation During maintenance bypass operation, the critical load is supplied directly by utility/mains power. While the UPS system is in maintenance bypass operation, a single-line diagram will appear on the screen. The orange line indicates the power flow from the utility/mains, and then to the critical load via the Q3 switch. Note: The batteries are not available as an alternate power source while the UPS system is in maintenance bypass operation.
Autostart Countdown The system can be set up for an automatic start when AC utility power is restored following a low battery voltage shutdown. The autostart countdown window is shown over all screens until the countdown period expires or the autostart is manually stopped by pressing the stop button. This feature is disabled by default and is not supported in parallel systems. Contact APC if this feature should be enabled.
Operation Procedures Access Screens Protected by User Password 1. When prompted for the user-password, press the password field to access the keyboard. 2. Type in the user password and press Enter. Note: On installation, the user password is set to “apc”.
Start Up System from Maintenance Bypass Operation Note: Start-up condition: The load is supplied via the Q3 switch from the utility/mains, and the other breakers are open. 1. Close the UPS input breaker (Q1). This will power up the UPS display. 2. Press the UPS System button in the bottom left corner to access the UPS System screen. Single System Parallel System 3. Press the Operation button. Type in the user password and complete with Enter. 4. Press System Start-up button.
5. Follow the steps which appear on the screen. Steps will appear in the order in which they need to be completed. A step will initially appear in red and then when it is completed, the step will change to green. The next step to be completed will be highlighted in red text and yellow background. Note: Grey buttons are touch-screen functions. Single System Parallel System 6. Check that the UPS Mode is Normal Operation in the upper right corner.
Shut Down System from Normal to Maintenance Bypass Operation Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS System button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the Operation button. Type in the user password and complete with Enter. 3. Press the System Shutdown button on the Operation screen.
4. Follow the steps which appear on the screen. Steps will appear in the order in which they need to be completed. A step will initially appear in red and then when it is completed, the step will change to green. The next step to be completed will be highlighted in red text and yellow background. Note: Grey buttons are touch-screen functions. Single System Parallel System Note: The display will turn off when the UPS input breaker (Q1) is opened.
Transfer from Normal to Requested Static Bypass Operation Note: Following this procedure will transfer the entire parallel system to requested static bypass. Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS system button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the Operation button. Type in the user password and complete with Enter.
3. Press the Normal Op. → Static Bypass button. Single System Parallel System 4. Press the Initiate Transfer button to go to static bypass operation. The Initiate Transfer button is greyed out when the transfer is not available. 5. Check that the status has changed to Requested Static Bypass in the upper right corner. Transfer from Requested Static Bypass to Normal Operation Note: Following this procedure will transfer the entire parallel system from requested static bypass to normal operation.
1. Press the UPS System button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the Operation button. Type in the user password and complete with Enter. 3. Press the Static Bypass -> Normal Op. button on the Operation screen. Single System Parallel System 4. Press the Initiate Transfer button to go to normal operation. The Initiate Transfer button is greyed out when transfer is not available. 5.
Isolate this Single UPS from the Parallel System Note: Before you start this procedure, ensure that the remaining UPS units can supply the load. Note: This procedure is only applicable to parallel systems. Note: Press the home button to go to the Parallel System Summary screen. 1. Press the UPS System button in the bottom left corner to access the UPS System screen. 2. Press the Operation button. Type in the user password and complete with Enter.
3. Press the Isolate this UPS button on the Operation screen. 4. Follow the steps which appear on the screen. Steps will appear in the order in which they need to be completed. A step will initially appear in red and then when it is completed, the step will change to green. The next step to be completed will be highlighted in red text and yellow background. Note: Grey buttons are touch-screen functions. Note: The display will turn off when the UPS input breaker (Q1) is opened.
3. Press the UPS System button in the bottom left corner to access the UPS System screen. 4. Press the Operation button. Type in the user password and complete with Enter. 5. Press System Start-up button.
6. Follow the steps which appear on the screen. Steps will appear in the order in which they need to be completed. A step will initially appear in red and then when it is completed, the step will change to green. The next step to be completed will be highlighted in red text and yellow background. 7. Check that the UPS Mode has changed to Normal Operation in the upper right corner.
See: See the Security Handbook, available on the APC Network Management Card Utility CD or from the APC Web site, www.apc.com, for more information on selecting and configuring network security. Operate the APC Battery Breaker Manually 1. Turn the selector to Manual position. 2. Check the spring status: a If CHARGED SPRING, go to step 3. b If DISCHARGED, charge the spring by pressing the bottom part of the handle to release it and pumping the handle a few times until the spring status says CHARGED SPRING.
Configuration Access the User Configuration Screen The UPS system is configured from the password-protected user configuration area of the display. 1. Press the UPS system button in the bottom left corner to access the UPS System screen Single System Parallel System 2. Press the Configuration button to access the Configuration screen. 3. Press the User Configuration button on the Configuration screen.
Perform a Battery Runtime Calibration Recalibrating the batteries keeps measurements like runtime and battery charge accurate. 1. Go to the User Configuration screen by following the steps in “Access the User Configuration Screen“. 2. Press the Battery Test Settings button on the User Configuration screen to access the Battery Test Settings screen. 3. Press Start to begin the battery runtime calibration. The batteries must be 100% charged to start a calibration.
The test lasts for approximately 10% of the available runtime. 1. Go to the User Configuration screen by following the steps in “Access the User Configuration Screen“. 2. Press the Battery Test Settings button on the User Configuration screen to access the Battery Test Settings screen. 3. Set the battery test settings a Battery self-test: Press Start to begin the battery self-test immediately. You can press Cancel to stop the self-test and continue in normal operation.
Set the Display Settings 1. Go to the User Configuration screen by following the steps in “Access the User Configuration Screen“. 2. Press the Display Settings button on the User Configuration screen to access the Display Settings screen. 3. Set the display settings: a Brightness: Place the finger on the indicator and slide it left or right to the desired setting. b Temperature unit: Select C for Centigrade or F for Fahrenheit.
Set the Network Management Card (NMC) Settings 1. Go to the User Configuration screen by following the steps in “Access the User Configuration Screen“. 2. Press the NMC Settings button on the User Configuration screen to access the NMC Settings screen. 3. The NMC Settings screen displays the configuration for each NMC in the system. Press the Configure NMC Settings button to access the Configure NMC Settings screen and to change the settings. 4. Change the NMC settings.
b Network settings mode: Select to use DHCP, BOOTP, or manual IP address. c IP address: Enter a valid IP address for the card. Only visible if manual mode has been selected. d Subnet mask: Enter a valid subnet mask. Only visible if manual mode has been selected. e Gateway: Enter a valid gateway. Only visible if manual mode has been selected. 5. Press the arrow down button and change the settings. a Select the Enable Modbus RTU box to enable the use of Modbus RTU.
3. Change the user password: a Press the Enter current password field and type the current password by using the keyboard on the screen. Complete with Enter. b Press the Enter new password field and type the new password by using the keyboard on the screen. Complete with Enter. c Press the Confirm new password field and re-type the new password. Confirm with Enter. 4. Press Apply to complete the password change procedure. Set the Alarm Settings 1.
3. Set the threshold values that must trigger the alarms: Note: For parallel systems, shared settings are marked with *. Single System Parallel System a UPS module redundancy: Set the system threshold for generating alarms in the redundant power modules. N+0 indicates that the redundancy alarm is disabled. N+1 indicates that there must be one redundant power module. b Parallel system redundancy: Set the number of redundant UPS units in a parallel system.
7. This screen is only visible if subfeed breakers are present. Set the load percentage for each subfeed breaker that should generate a warning alarm. 8. Press Apply to confirm the settings. Set the System Time Note: The date and time will be synchronized between the UPS units in a parallel system. 1. Go to the User Configuration screen by following the steps in “Access the User Configuration Screen“. 2.
3. Set the system date and the system time. 4. Press Apply to confirm the settings. Set the Language and Regional Settings Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS system button in the bottom left corner to access the UPS System screen Single System Parallel System 2. Press the Language button to access the Language Settings screen.
3. Select the preferred language. 4. Select your preferred date format and temperature unit and complete with Finish.
Maintenance Access Predictive Maintenance Screen Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS System button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the System Information button on the UPS System screen.
3. Press the Predictive Maintenance button to access the Predictive Maintenance screen. 4. The Predictive Maintenance screen shows the status and the estimated remaining lifetime of the power modules and their fans. The status can be OK, Near end, or Exceeded. Remember to order new spare parts or schedule a maintenance visit when the status is Near end.
Return Parts to APC Call APC Customer Support to obtain an RMA number. To return a failed module to APC, pack the module in the original shipping materials, and return it by insured, prepaid carrier. The APC Customer Support representative will provide the destination address. If you no longer have the original shipping materials, ask the representative about obtaining a new set. Pack the module properly to avoid damage in transit.
APC recommends that a whole battery module (one row of batteries) is replaced at the same time to ensure optimal run-time (see Example 1). However it may only be necessary to replace three battery units at the same time according to Examples 2 and 3 in the table below.
Replace Batteries Use two people to lift components weighing between 18–32 kg (40–70 lbs). 1. Holding the handle, gently lift the battery unit Battery Enclosure and pull it halfway out. A lock mechanism prevents it from being pulled all the way out. 2. Release the lock by pushing the battery unit upwards and pull the battery unit all the way out while you continue to support its weight. 3. Carefully guide the new battery unit into the system.
1. Identify the faulty power module via the display or the red LED indication in the top right corner of the power module. 2. Deactivate the power module by turning the locking latch counter-clockwise to the unlocked position. 3. Unscrew the spring-activated knobs on both sides of the power module. 4. Pull the power module up and out of the enclosure as far as the lock mechanism allows. 5.
9. Activate the power module by turning the locking latch clockwise to the locked position. The LED in the top right corner of the power module will start to flash (green) which indicates that the power module is initializing and doing a self test. When the self test is complete, the LED will be constant green.
Replace Boards in Input/Output/Bypass Enclosure WARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components. WARNING: Before replacing the boards, ensure that the “UPS system firmware version” and the “System firmware version stored at memory card” are identical on the System Information screen. WARNING: Replace only one board at a time.
Replace Boards in the Battery Enclosure WARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components. WARNING: Replace only one board at a time. 1. Loosen the two/four screws in the corners of Battery Enclosure the board. a Battery motor breaker PSU. b System power supply. c Top-half battery monitoring board. d Bottom-half battery monitoring board.
Troubleshooting Alarms The color of the top of the screen switches from blue to red and an alarm button is shown when an alarm situation occurs. Alarm Button Press the alarm button to go to the Active Alarms screen that displays all active alarms, along with a corrective action for addressing each alarm. When you press the alarm button, the alarm will automatically be silenced. Alarm Levels Info Informational alarm. No immediate action required. Check the cause of the alarm as soon as possible.
Critical Take immediate action. Call APC for instructions. View the Active Alarms 1. Press the Alarm button on the top bar when an alarm situation occurs. 2. A list of the active alarms is shown on the screen. Press the Location button to see the location of the particular module. Press the Graph button to see voltages and currents at the time the alarm was generated. The three alarm severity icons display at the top of the screen with numbers indicating how many times each severity type has occurred.
View the Event Log Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. The Event Log screen can be accessed either by pressing the Event Log button on the Active Alarms screen see “View the active alarms” or by following this procedure: 1. Press the UPS system button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the System Information button on the UPS System screen. 3.
4. Active in control indicates which intelligence module is in control of the system. Press the Active Event Log button to view the records from the intelligence module in control or press the RIM Event Log to view the records from the intelligence module that is passive. 5. The Recent Events log contains a detailed record of the 32 latest events. Press the Full Log button to see the 10000 latest events and access the Save Log button. 6.
7. Select to filter the events by source, location and/or timestamp and press OK. 8. Set your filter parameters and press OK to initiate the filtering. 9. To save the log, insert a USB flash drive into the USB port on the display. Note: Do not remove the USB flash drive before a dialog box on the display indicates that it is safe to remove the USB flash drive.
10. Press the Save Log button. The full event log is saved as a text and an HTML file. Associated event capture files are also saved. All files are saved in a single compressed Zip-file to the USB flash drive. Bookmark an Entry in the Event Log A maximum of five entries can be bookmarked in the system. 1. Double press on an event in the event log to bookmark a log entry. 2. Bookmarked entries are highlighted in a darker background colour. 3. Press the Bookmark symbol to cycle through the bookmarks.
You can choose to remove all existing bookmarks by pressing the Remove All button or click Cancel to remove them one by one. Press twice on the log entry to clear a bookmark. View and Save Information about Firmware Version Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS system button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the System Information button on the UPS System screen.
3. Verify that the “UPS system firmware version” and “System firmware version stored at memory card” are identical. Press the Firmware Overview button. 4. To save the firmware version list, insert a USB flash drive into the USB port on the display. Note: Do not remove the USB flash drive before a dialog box on the display indicates that it is safe to remove the USB flash drive.
5. Press the Save FW*Versions list button to save the firmware version list as an HTML file. Press the button in the location column to open the Module Status Details screen for the particular module. Reboot the Display 1. Press the reboot button at the bottom of the display to reboot the display.
Worldwide Customer Support Customer support for this or any other product is available at no charge: • Contact the Customer Support Center by telephone or e-mail. For local, country-specific centers: go to www.apc.com/support/contact for contact information. © APC by Schneider Electric. APC and the APC logo are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.