RESET PARAMETERS
Reset allows the user to reset the parameters in a particular sensor to the factory
defaults.
To reset the parameters in sensor number 1, use the command structure:
Send
AAh Start Byte
01h, Sensor Number
1Fh Command
00h NA
00h NA
55h End Byte
MOUNTING
When mounting any ultrasonic sensor, alignment is critical. Ensure the face of
the transducer is parallel to the target. A misalignment of a few degrees can
affect the accuracy and reliability of the sensor.