user manual Owner's manual

MNU Series Ultrasonic Sensors Rev. B1, 5/13
18
Automa! on Products Group, Inc.
APG...Providing tailored solu• ons for measurement applica• ons
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Parameter Descrip! ons
Device Address (1 to 255) (40400)
Each device within the Modbus network must be assigned a unique address.
Each MNU sensor should be connected to the network individually and as-
signed an address. By default the each sensor is set to address 1.
Units (1 to 3) (40401)
Determines the unit of measure for the Calculated Reading (input registers
30303-30304) when in Applica! on Types 1, 2 or 7 (see below).
Applica! on Type (0 to 11) (40402)
Determines how the sensor calculates the readings.
Applica! on Type 0: Distance to target
(measurement result in register 30300)
Register Func! on Value Range
40401 Units 1 to 3
40402 Applica! on Type 0
40404 Decimal Place 0 to 3
40405 Max Distance 0 to 10364 mm
Applica! on Type 1: Depth of level
(measurement result in register 30300)
Register Func! on Value Range
40401 Units 1 to 3
40402 Applica! on Type 1
40404 Decimal Place 0 to 3
40405 Max Distance ≥ Empty Distance
40406 Full Distance Typically = Blanking Distance
40407 Empty Distance 0 to 10364 mm
Distance
Level