user manual Owner's manual

Rev. B1, 5/13 MNU Series Ultrasonic Sensors
27
Automa! on Products Group, Inc.
APG...Providing tailored solu• ons for measurement applica• ons
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Applica! on Type 11: Curve Fit (Strapping Chart)
Allows the sensor to mimic a tank strapping chart by using a 3rd degree polyno-
mial equa! on to produce a “curve fi t” approxima! on.
(measurement result in register 30303-30304)
Register Func! on Value Range
40401 Units 1 to 3
40402 Applica! on Type 11
40404 Decimal Place 0 to 3
40406 Full Distance Typically = Blanking
40407 Empty Distance 0 to 10364 mm
40436-40437 Parameter 1 0 to 100,000 mm
40438-40439 Parameter 2 0 to 100,000 mm
40440-40441 Parameter 3 0 to 100,000 mm
40442-40443 Parameter 4 0 to 100,000 mm
Open the APG Modbus so# ware and select “Strapping Chart” from the “Tools”
menu.
Enter the desired data points
into the table.
Use the “Load” bu$ on to re-
call a previously saved table.
Import data from an electronic
document by copying the data
and then using the “Paste”
bu$ on to populate the table.
OR
OR