When the MNU is interfaced with an LOE or RST-5002 web-enabled master
device, it can be con gured to generate website alarms via levelandfl ow.com
(refer to the LOE or RST-5002 user manual for more informa# on about website
alarms and using levelandfl ow.com).
Trip Alarm 1 (40430) or Alarm 2 (40433) Distance
Sets the level (in mm), beginning the bo$ om of the stem, to the fi rst (lowest)
actua# on point (refer to next page for more informa# on).
Trip Alarm 1 Window (40431 or 40434)
Sets the level (in mm), beginning from the Trip Distance loca# on, to the second-
ary actua# on point (refer to next page for more informa# on).
Trip Alarm 1 Type (40432 or 40435)
Determines the opera# onal logic performed by the Trip Alarm (refer to chart on
next page for more informa# on).
Confi guring Trip Alarm Types for Website Alarming:
(refer to Trip Types chart on next page)
Placing a “1” in front of any of the Trip Types designates an ac# ve trip point as
an alarm condi# on. For example; Trip Type 3 would be designated as 13, and
would ini# ate a website alarm whenever the trip is ac# ve (on).
Placing a “2” in front of any of the Trip Types designates an inac# ve trip point as
an alarm condi# on. For Example; Trip Type 3 would be designated as 23, and
would ini# ate a website alarm whenever the trip is inac# ve (off ).