Installation Guide
Conbraco Industries Inc. Pageland S.C. 29728 Telephone (704) 847-9191 Apollovalves.com
Troubleshooting
SYMPTOM POSSIBLE REASONS SOLUTION
Press cycles
produced are
not complete.
Wrong jaw set or press ring for the
tube size or material.
Install correct jaw set.
The jaw set or ring was not square
to the tube.
Redo the joint with new tube and
valve and make sure that the jaw set
or ring is square to the valve.
Jaw contour was not aligned with
the valve contour.
Redo the joint with new tube and
valve and make sure that the jaw set
or ring is square to the valve.
The jaw set or ring has exceeded life
expectations and may have failed.
If cracked, replace old jaw set with a
new jaw set and redo the joint using
a new tube and valve.
Excessively large
or sharp fins
present at press
joint parting line
where jaw or
ring tips come
together.
Copper material build-up on jaws or
rings in the contoured profile area
near jaw or ring tips.
Clean jaw sets or rings in the
contoured area using metal
polishing pads such as Scotch-Brite®.
Refer to the press tool's
maintenance section for proper
instructions
Excessively worn or damaged jaw
sets or rings.
Discard jaws or press ring and
replace with a new jaw set.
Jaws stick to
valve excessively
after completing
joint.
Copper material build-up on jaws or
rings in the contoured profile area
near jaw or ring tips.
Clean jaw sets or rings in the
contoured area using metal
polishing pads such as Scotch-Brite®.
Refer to the press tool's
maintenance section for proper
instructions
OPERATION
The valve handle is marked showing proper rotation direction for “ON” and “OFF” positions. Standard rotation is clockwise for
“OFF” (closed) and counterclockwise for “ON” (open).
MAINTENANCE
Normal stem packing wear can be compensated for by tightening the packing gland nut. The top nut and the lever
may need to be removed for easy access to the packing nut. Tighten the packing nut clockwise in 1/8 turn increments until
observed leakage stops. (Packing wrench part number H371400 is available to ease this operation.) Reinstall the handle
and handle nut after adjustment.
FOR NON-LEAD FREE VALVES: It is illegal to use this product in the United States for potable water services
(water intended for human consumption).
FOR LEAD FREE VALVES: This product complies with U.S. Safe Drinking Water Act (SDWA). Suitable for potable
water applications intended for human consumption.