Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware Specifications 7 4.0 Software Specifications 14 5.0 Panel Enhancements 18 6.0 Compatible Field Devices 20 Appendices i Other Relevant Documentation Document Ref: Dis4app.doc / Rev 0 25.7.
1.0 Introduction and Typical System Illustration The Discovery analogue addressable panel is available as a 1-4 loop panel using plug-in loop driver cards. Each loop is rated at 500mA and will control up to 126 Apollo, XP95 or Discovery devices. All addresses may be configured as cause/effect outputs, with up to 255 different programmable groups and 3 independently programmable output bits per address.
FIR BR BAR LO OL OR AP LAT S AN TR R ITO MON CH UPT WIT RR I S NTE MIINTH I W ISOLATOR AY REL 44 A1 EA K SS GLAS HE S RE REM A FIR OTE I /7 44 14 45 14 M BEA E GLA ES S SS HE 5 44 A1 RE 5 44 A1 S UI NG TI M EX STE SY SS HE RE EA AR ER & T UL FA MS AR AL YS LA RE ER AMPG E DRIN FIORNITO M EAK PR S NG HI FIR BR RE FI S AL ON TI EN NEL NV PA CO RE FI L NE PA SS D AM AN OGR AD PR LO D UP LOA PC WN DO RE K OR TW NE ER AT PE RE 1 2 3 4 5 6 7 8 TH O WI I/ K L NE OR
2.0 Cabinet Specifications 2.1 Surface Cabinets All cabinets are manufactured from 18SWG sheet steel and finished in satin texture epoxy powder stove paint. Top entry grommets and rear entry knockouts are provided.
2.2 Semi-Flush Bezels The semi-flush bezel locates to the rear of the bevelled edge of the back box, leaving the bevelled edge and door raised out from the wall. Finished in the same colour as the cabinet back box and fitted by means of pinch bolts, thus avoiding the need to drill the cabinet.
2.3 Fully Flush Bezel Fixed to the standard cabinet back box in place of the door and sized larger than the back box. Available in polished or brushed brass, stainless steel and painted finishes.
3.0 Hardware Specifications 3.1 Mechanical Assembly Illustration CHASSIS MOTHERBOARD CABINET LOOP CARDS DISPLAY DOOR POWER SUPPLY BATTERY SET (SEE BATTERY CALCULATION SPREADSHEET) PRINTER Document Ref: Dis4app.doc / Rev 0 25.07.
3.2 User Controls & Indications 20 character by 4 line LCD display. Back-lit when event present or Access controls switch ON. 1 EVACUATE OVERRIDE DELAY 2 SCROLL MESSAGES SILENCE BUZZER 3 TEST ALARMS SILENCE / RESOUND ALARMS 4 TEST DISPLAY RESET 5 ACCESS MENU MENU UP 6 MENU DOWN User controls. Only override delay is available without operating the access controls keyswitch User indications ESCAPE < ENTER > Switch to 1 to enable controls (enter level 2).
3.2.1 User Controls and Indications in Detail Operates all sounder circuits continuously 1 Displays the next message at the current event level Activates all alarm outputs when pressed. Alarms silenced when released Tests all indications and internal buzzer Enters the user menu system for access to further level 2 and level 3.
3.3 Engineer’s Facilities Fit link to enable earth fault monitoring. Remove link to enable earth fault monitoring. Move switch to right to enable changes to site specific data. Move switch to left to disable when changes complete.
3.4 Power Supply PROC BATT L/BATT TEST LAMPS PROC FAULT RESET PSU OK EARTH 5/8V RESET PROC MAIN THERM FAULTS JP2 SW1 EARTH FAULT DISABLE TEST LAMPS PROC FAULT RESET PSU OK RESET PROC SW2 JP1 EARTH CAP DISABLE Document Ref: Dis4app.doc / Rev 0 25.07.
3.5 Use of Auxiliary Inputs Auxiliary inputs are provided to allow remote operation of the following functions: • Fault • Evacuate • Silence • Reset Each input circuit is fully monitored for open and short circuit faults. To activate an input a 680 ohm resistor should be connected across the input circuit by a normally open switch contact. Two switches are shown in Figure 1 although there is no limit to the number of switches.
3.
4.0 Software Specifications 4.1 Overview of Engineers Functions This section describes an overview of the functions available to the end user. 4.1.1 Changing Time and Date The user can manually set the time and date although this should not normally be required. The current time is maintained by a dedicated battery when all power removed from the system. How to set the time and date is described in the user manual. 4.1.
Note: The default levels are: Default Alert level Default Fire level Valid Alert Levels Valid fire levels Default sensitivity levels Valid sensitivity levels XP95 sensor 45 55 35, 40, 45, 50 55, 60, 65, 70 N/A N/A Discovery sensor 45 55 35, 40, 45, 50 55 3 1, 2, 3, 4, 5 All ancillary devices have fixed responses except the Apollo Input Output module. The input for this device can be configured for response as a fire, fault, alert or indication only. 4.1.
The zone and group based events can occur on any device, or devices within the specified zone or group: • Fire in a group or zone, output cleared on silence alarms. • Fire in a group or zone, output cleared on reset. • Any two fires in a group or zone, output cleared on silence alarms. • Any two fires in a group or zone, output cleared on reset. • Alert in a group or zone, output cleared on reset. • Fault in a group or zone, output cleared on reset.
4.
5.0 Panel Enhancements The Discovery 1-4 loop panel may be enhanced to provide additional facilities. Other relevant documentation is available providing more details. A1535 (8 WAY RELAY CARDS) AND A1536 (8 WAY ALARM CARDS) UPTO 31 CARDS PER PANEL DISCOVERY 1-4 LOOP PANEL REPEATER PANELS NE ZONE ZONE ZONE ZONE ZONE ZONE ZONE ZO 1 2 3 4 5 6 7 8 KONEX NETWORK REPEATER WITH I/O EXPANSION PC PROGRAMMING ALARM MANAER GRAPHICS SYSTEM Note: This is an illustration only and not wiring schematic.
5.1.2 A1535/A1536 8 Way Expansion Boards Up to 31 (A1535 & A1536) 8 way programmable expansion boards may be connected to each Discovery 1-4 loop panel. A special 2 door cabinet is available to house up to 4 enhancement boards (details on request). Up to 31 boards in total may be connected via an RS485 comms - for local expansion only. Local power is required for each board in addition to the RS485 comms link.
The Discovery is approved with the devices listed in this section. The other compatible devices are listed in section 6.
6.
Part No Description 55000-640 XP95 I.S. Optical smoke detector (Apollo manufacture) 55000-440 XP95 I.S. Temperature detector - standard (Apollo manufacture) 55000-940 XP95 I.S. Manual call point (Apollo manufacture) 45681-215 XP95 I.S. Base (Apollo manufacture) 6.2 General Accessories’ Order Codes & Descriptions Part No.