Specifications

Document Ref: Dis4app.doc / Rev 0 25.07.00 Page 13 of 22 Originator MC Checked__AC_
3.7 Mechanical and Environmental Specification
Size: Height:
Width:
Depth:
480mm
410mm (2 loop and network repeater)
160mm including lock and indented holes
Weight excluding batteries: 15kg
Operating temperature: -5ºC to 40ºC
Operating humidity: 5% to 95%
Electrical
Mains voltage: 230V AC +10%/-15%
Mains failed fault battery current:
1 Loop:
2 Loop:
3 Loop:
4 Loop:
145mA
170mA
195mA
220mA
Mains failed alarm battery current:
1 Loop:
2 Loop:
3 Loop:
4 Loop:
260mA
285mA
310mA
335mA
Battery charger type: Adjustable 27.5V float charger.
Maximum battery charging
current:
1.5A
Battery type: 2 off 12V 12AH sealed lead acid standby battery
Battery size: 151mm x 98mm x 97.5mm
Panel inputs
Remote Fault: Fully monitored circuit, 3k9 EOL, 680R active
Remote Evacuate: Fully monitored circuit, 3k9 EOL, 680R active
Remote Silence: Fully monitored circuit, 3k9 EOL, 680R active
Remote Reset: Fully monitored circuit, 3k9 EOL, 680R active
Panel outputs
For each loop: LO+ Loop out +ve
LO- Loop out –ve
LI+ Loop return +ve
LI- Loop return –ve
Alarm circuits 2 at 1A per circuit
Auxiliary supply: 18.8V-28V @ 500mA