Specifications
Document Ref: Dis4app.doc / Rev 0 25.07.00 Page 15 of 22 Originator MC Checked__AC_
Note: The default levels are:
XP95 sensor Discovery sensor
Default Alert level 45 45
Default Fire level 55 55
Valid Alert Levels 35, 40, 45, 50 35, 40, 45, 50
Valid fire levels 55, 60, 65, 70 55
Default sensitivity levels N/A 3
Valid sensitivity levels N/A 1, 2, 3, 4, 5
All ancillary devices have fixed responses except the Apollo Input Output module. The input
for this device can be configured for response as a fire, fault, alert or indication only.
4.1.5 Discovery Device Functions
The following functions are available with Apollo Discovery devices:
• Print drift compensation level by loop
• Print device date of manufacture
• Enable or disable LED pulsing mode
4.1.6 Zone Allocation
The Discovery has 32 programmable zones. All loop devices can be programmed into one of
these zones through the engineers menu. Activation of a fire or a fault on a device will cause
operation of the fire or fault indicator associated with the zone. The panel alphanumeric
display will also indicate the zone number. The panel has an insert fitted to the front door
suitable for text descriptions of each zone location.
The engineer can also print out all the zones with the devices allocated to the zones.
4.1.7 Programmable Cause/Effect
Any loop device output can be individually programmed to operate in response to a common
event or a zone or group entering a specific condition.
The common events are: -
• Common fire, output cleared on reset
• Common fire, output cleared on silence alarms
• Common alert, output cleared on reset
• Common fault, output cleared on reset
• Common indication, output cleared on reset
• Alarms silenced
• Panel reset
• Evacuate (including remote evacuate)