User Guide

The Loop connector on the top of the translator board should
be wired to the Panel of your choice, from the left to right
the terminals are:
• Loop Out Positive wired to Loop In Positive on the Panel
• Loop Out Negative wired to Loop In Negative on the Panel
Screen
Screen
• Loop In Positive wired to loop Out Positive on the Panel
• Loop In Negative wired to Loop Out Negative on the Panel
7
9
8
The translator will power up and the translator will be
Follow the step by step instructions on the screen
to complete the system setup.
ready for commissioning phase.
• Screw the lid to the back box using the supplied plastic
screws and refit top and bottom front plastics that cover
screw housings.
LOOP OUT (+)
LOOP OUT (-)
SCREEN
LOOP IN (-)
QUICK START GUIDE
RW1700-030APO
REACH XP95 Loop Interface Module
Apollo Fire Detectors Ltd. 36 Brookside Road, Havant, Hampshire, United Kingdom, PO9 1JR
T: +44 (0)23 9244 2706 - E: techsales@apollo-fire.com - W: www.apollo-fire.co.uk
RW_IG_LOOP_INTERFACE_REV_A.2
GREEN LED
SCREEN
LOOP IN (+)