Installation Guide
The NAC Module monitors and controls a circuit of alarm notification appliances or speakers. It is
mounted on a plastic face plate for use with a UL listed 4” square or 2 gang electrical box (minimum
depth 2⅛”). The module requires a separate 24V DC supply to power notification appliances.
In addition to individual NAC Module operation, multiple modules can be controlled simultaneously as a
group*. A green LED flashes in synchronization with the current pulse reply from the device.
Please Note:
• *Physical group addressing feature is only available in XP95/Discovery Protocol.
• The NAC Module is designed for
indoor dry use only
.
APD0834 / 2021 / ISSUE 3
INSTALLATION GUIDE
SOTERIA UL
NAC MODULE
1
GENERAL
Part Number SA4705-706APO
Replacement Part Number 55000-825
Type Sounder Control Module
Dimensions 4.9” width x 4.9” height x 1.175” depth
Temperature Range 32°F to 120°F (0°C to 49 °C)
Humidity 0 to 95% RH (Non-Condensing)
Signal Line Circuit (SLC) Supervised
Operating Voltage 17-28V DC
Modulation Voltage
Supervisory Current
LED Current
Maximum Loop Current
Approvals
Material
TECHNICAL INFORMATION
All data is supplied subject to change without notice. Specifications are typical at 24V, 25°C and 50% RH
unless otherwise stated.
CONTROL PANEL COMPATIBILITY
The NAC Module has been approved by UL, LLC. For details of compatible panels contact Apollo
America Inc. For NAC circuit, contact Panel manufacturer for compatibility details
Max Standby Current (Pulsing LED)
Max Surge Alarm Current (LEDs on)
5-9 V (peak to peak)
<700 µA
1.6mA per LED
1A
UL, ULC, CSFM, FM
UL 94 V-0
2.96 mA
4.8 mA
Wire Range
12-24 AWG