Cut Sheet

NEMA 3, 3R, 4, 4X
Plugs and Receptacles
Plugs and RecePtacles: ORdinaRy lOcatiOn
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
798
Powertite
®
200 Amp Pin and Sleeve Spring Door Plugs and Receptacles
600 Vac, 250 Vdc, 50-400 Hz.
Wire Recess Diameter: .687”. Wire Size Range: 250 MCM-#2/0. Pressure Wire Terminals
.
Grounding
Style Wire/Pole
Receptacle with AJA
Mounting Box
Hub Size
(Inches)
Receptacle
Only
Plug
Only
Cable Dia.
(Inches)
Style 1
(Shell Only)
3W, 3P
ADJA20033-150 1-1/2
ADR20033
AP20033CD .875 to 1.906
ADJA20033-200 2
AP20033E 1.875 to 2.500
ADJA20033-250 2-1/2
4W, 4P
ADJA20044-200 2
ADR20044
AP20044CD .875 to 1.906
ADJA20044-250 2-1/2 AP20044E 1.875 to 2.500
Style 2
(Shell and
Extra Pole)
2W, 3P
ADJA20023-150 1-1/2 ADR20023 AP20023CD .875 to1.906
ADJA20023-200 2
ADR20023 AP20023E 1.875 to 2.500
ADJA20023-250 2-1/2
3W, 4P
ADJA20034-150 1-1/2
ADR20034
AP20034CD .875 to1.906
ADJA20034-200 2
AP20034E 1.875 to 2.500
ADJA20034-250 2-1/2
For Reverse Service add suffix -RS to Catalog Number.
For Special Polarization, add suffix -P4 to Catalog Number.
Maximum Conductor Size
Wire Recess
Dia. (Inches) Conductor Size Max. Strand Type Conductor
0.687
250 MCM 37 General Wire
4/0 19 General Wire
4/0 259 Flexible Cable
3/0 427 Extra Flexible Cable
2/0 259 Flexible Cable
2/0 259 Flexible Cable
Horsepower Ratings for Emergency Disconnect Under Load
Plug may be withdrawn in an emergency if within these maximum HP ratings. Not for normal starting and stopping,
Motor Phase Wire/Pole
Motor Horsepower
120 Vac 240 Vac 480 Vac 600 Vac
1-Phase 2W, 3P 15HP 30HP 40HP 40HP
3-Phase 3W, 3P; 3W, 4P; or 4W, 4P 20HP 40HP 50HP 50HP
Adapters for #4-#1 wire available, see Powertite
®
200 and 400 Amp Replacement Parts.
For additional mounting boxes, see Aluminum Mounting Boxes.
† Receptacle meets NEMA 3R with spring door closed and NEMA 3, 3R, 4, 4X with plug fully inserted and wing nuts fully tightened or cover closed with wing nuts
fully tightened.