Cut Sheet

Areamaster
Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
Electrical Ratings
Voltage Suffix Voltage (V) Input Power (Watts)
Input Current
(Amps) Power Factor (PF)
Total Harmonic
Distortion (THD) Model Number
BU
120Vac 180 1.52
>.9 <20%
AMLHL1
277Vac 176 0.67
170Vdc 172 1.02
N/A N/A
300Vdc 170 0.57
BH
347Vac 179 0.52
>.9 <20%
480Vac 179 0.39
BU
120Vac 231 1.94
>.9 <20%
AMLHL2
277Vac 231 0.88
170Vdc 220 1.30
N/A N/A
300Vdc 217 0.72
BH
347Vac 219 0.64
>.9 <20%
480Vac 219 0.47
BU
120Vac 317 2.67
>.9 <20%
AMLHL3
277Vac 303 1.15
170Vdc 305 1.80
N/A N/A
300Vdc 298 0.99
BH
347Vac 299 0.87
>.9 <20%
480Vac 298 0.63
Surge Protection: Integral 6KV surge protection. Option for up to 10KV surge protection. (cCSAus only).
All ratings are typical.
Luminaire Category Image
Frontal Projected Area
(FPA) ft
2
Drag Coefficient
(DC)
Effective Projected Area
(EPA) = FPA*DC ft
2
90°toGround-Worst
CaseMounting
2.04 1.20 2.45
45°toGround-Standard
Mounting
1.44 1.20 1.73
Wind Direction
Wind Direction
NEC/CEC:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2 Group IIC
Class II, Division 1 and 2, Groups E, F, G
Class III
Zone 20 and 21 Group IIIC
NEC/CEC:
Zone 22, Group IIIB
Simultaneous Exposure
Marine Outside Type (Salt Water) for USA ONLY
Wet Locations
Type 3R, 4, 4X, IP66/67
ATEX/IECEx:
Zone 2, 22
IP66
II 3GD
IK10
Ex ec llC T4
LED/FLooDLights: NEC/CEC, AtEx/iECEx ENCLosED AND gAskEtED
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© April 2018
278