Cut Sheet
Plugs and RecePtacles: nec/cec ORdinaRy lOcatiOn
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© March 2019
462
Powertite
™
Series Pin and Sleeve Plugs, Connectors and Receptacles
Range of Wire Sizes Accommodated in Powertite™ Plug and Receptacle Terminals
60 °C (140 °F) minimum wire ratings.
30, 60, 100, and 150 Amp 200 Amp 400 Amp
Amps
Wire Recess
Dia. (Inches)
Wire Range
Wire Recess
Dia. (Inches)
Conductor
Size
Type
Conductor
Solder Recess
Dia. (Inches)
Conductor
Size
Type
ConductorBuilding Extra Flex.
30 .281 #10 – #6 #10 – #8
0.687
250 General Wire
0.84
500 MCM General Wire
60 .312 #6 – #2 #6 – #4 4/0 General Wire 400 MCM Flex. Cable
100 .391 #4 – #1 #4 – #2 4/0 Flex. Cable 400 MCM Extra Flex.
150
.525 #2 – 2/0 #2 – 2/0 3/0 Flex. Cable
1.25
1000 MCM General wire
3/0 Extra Flex. 900 MCM General Wire
2/0 Flex. Cable 800 MCM Extra Flex.
NEMA 4X.
For receptacle only.
Copper with beryllium copper springs.
Powertite™ Horsepower Ratings Plug may be withdrawn in an emergency if within these maximum HP ratings. Not for normal starting/stopping.
Motor Horsepower Motor Horsepower
Phase Motor Amps 115 Vac 230 Vac 480 Vac 600 Vac Phase Motor Amps 115 Vac 230 Vac 480 Vac 600 Vac
For Emergency Disconnect Only
3-Phase
3W, 3P;
3W, 4P;
or
4W, 4P
30 3 7-1/2 15 20
1-Phase
2W, 2P
or
2W, 3P
30 2 3 10 10
60 7-1/2 15 30 30 60 3 10 20 20
100 10 20 40 40 100 7-1/2 15 30 30
150 Do Not Disconnect Under Load 200 15 30 40 40
200 20 40 50 50
Application Chart
Grounding
Style Wire/Pole
Single Phase Grounding
Style Wire/Pole
Three Phase
With Neutral Without Neutral With Neutral Without Neutral
Style 1
(Shell Only)
2W, 2P L1+N+G L1+L2+G
Style 1
(Shell Only)
2W, 2P
3W, 3P L1+L2+N+G 3W, 3P L1+L2+L3+G
4W, 4P 4W, 4P L1+L2+L3+N+G
Style 2
(Shell and
Extra Pole)
2W, 3P L1+N+G L1+L2+G
Style 2
(Shell and
Extra Pole)
2W, 3P
3W, 4P L1+L2+N+G 3W, 4P L1+L2+L3+G
Features at a Glance
Receptacle Types Contacts Reverse Service
Amp
Grounding
Styles
Weatherproof
Spring Door
NEMA 4X
Screw Cap
Raintight
Clamp Cover
Brass with
Beryllium Copper
Springs
Copper with
Borosilicte
Bearings
Split-type
Copper
Contacts
Brass
Ground
Contacts
In
Field
Factory
Only
30 1 and 2 X X X Style 2 X
60 1 and 2 X X X Style 2 X
100 1 and 2 X X X Style 2 X
150 2 X X
X
Style 2 X
200 1 and 2
X
X
X Style 2
X
400 1 and 2 X Style 2 X
NEC/CEC:
Listed for Ordinary (Unclassied) Locations
NEMA 3, 3R, 4, 4X