ELS Series Emergency Lighting System
Explosionproof, Dust-Ignitionproof
Remote and direct mounted fixtures for hazardous location applications
Applications
• ELS Series features an emergency lighting power unit that is
designed to provide safe operation in the presence of hazardous
gases, vapors or dusts, dened by the National Electrical Code
as Class I, Groups C and D, and Class II, Groups E, F and G.
• Typical applications include all means of egress (such as
walkways, exit ramps, stairs and aisles) for hazardous areas
which include oil reneries, petrochemical facilities, pulp and
paper mills, chemical storage areas, wastewater treatment
facilities and grain elevators.
Features
• The electronics consist of a solid-state charger, transfer circuit
and low-voltage battery disconnect circuit.
• The unit test switch and AC “On” indicator light are housed in
a separate module that may be attached directly to the unit
housing or mounted remotely for ease of testing.
• All ELS Series units are rated for operation in NEC Class I,
Division 1 and 2, Groups C and D; and Class II, Division 1 and 2,
Groups E, F, and G environments.
• Housing provisions allow for the attachment of two optional
explosionproof lighting xtures.
• Unit capacity is sufcient for the connection of up to four 6- or
12- volt, 18-watt xtures.
• Units provide 90 minutes of emergency operation.
• The solid-state charger maintains battery at full charge.
• Upon failure of utility voltage, the DC emergency lighting load is
connected to the battery.
• During emergency operation, automatic battery protection from
deep discharge damage is provided by a low-voltage battery
disconnect (LVD) circuit.
• Upon restoration of normal power, the charger will begin a
recharge cycle. It will bring the battery to full capacity within
acceptable UL time standards.
• A pilot light indicates the presence of AC line voltage, and a test
switch is provided for checking transfer operation. Lock-out
type guard on push button accepts locks with up to 6.5 mm
(1/4 in) hasp.
• A universal transformer allows operation on 120 or 277 Vac
lines.
• Emergency power source is a maintenance-free, sealed,
pure-lead battery suited for harsh temperature environments
for 0 °C to +40 °C (+32 °F to +104 °F).
— Never necessary to add water.
— Expected life is 10 years
— Compact in design
• Standard illumination is provided during power failure only using
xtures specially designed for emergency lighting in hazardous
environments, supplied with double contact bayonet base 18-
or 28-watt incandescent lamps.
• Designed for easy installation. Provided with 4 mounting holes
for attachment to a wall or other suitable surface. Mounting
hardware not included.
• Housing is drilled and tapped for installation of utility
12.7 mm (1/2 in) NPT conduit.
• Quick access to internal wiring and components is provided
by thread-on cover.
• All necessary ttings for test switch/ pilot light module
supplied standard.
Standard Materials
• Battery enclosure, xtures, guards and pendant mount:
copperfree (4/10 of 1% max.) aluminum.
• Ceiling and bracket mounts: malleable iron with aluminum
adapter
• Reectors: porcelain enameled steel
• Test Switch: copperfree (4/10 of 1% max.) aluminum with
stainless steel hardware
Standard Finishes
• Enclosure, xtures and test station: epoxy powder coat
nish electrostatically applied for complete and uniform
surface protection
• Reectors: white porcelain enamel
Options
• The xture may be adapted to serve as an exit sign through use
of an Auxiliary Exit Housing.
• Time Delay Relay (15 minutes) available to permit normal
lighting to re-establish brightness. Add sufx -T1 for 120 Vac, or
-T2 for 277 Vac.
NEC Certifications and Compliances
• UL Standard: UL 924, UL 844, UL 1598
• UL Listed: 175025
NEC:
Class I, Division 1 and 2, Groups B , C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
Contact your sales representative for Class I, Group B rating.
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© May 2019