Cut Sheet

“T” Numbers Represent the Maximum Surface Temperature for Class I, Division 1 Locations and
Maximum Surface Temperature Under Dust Blanket for Class II, Division 1 Locations.
“T”
Number
T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
Temp.
Range
˚C)
351-
450
326-
350
301-
325
281-
300
261-
280
231-
260
216-
230
201-
215
181-
200
166-
180
161-
165
136-
160
121-
135
101-
120
86-100 85
Temp
Range
(°F)
664-
842
619-
662
574-
617
538-
572
502-
536
448-
500
421-
446
394-
419
358-
392
331-
356
322-
329
277-
320
250-
275
214-
248
187-
212
185
Fixtures are for use with Group B atmospheres only when used with Group B mounting hoods. For 26 W,32 W, and 42 W fixtures only.
Available only for 52, 64 and 84 watt fixtures.
Available in Codemmaster 2 Only
Certified to meet the Canadian Electrical Code (CEC) only.
Classified Area Suitability of Code•Master™ Series PLT Fixtures — Suitability includes use of reflector
Class I, Division 1 and 2 with Globe or
with Globe and Reflector
UL/NEC Temp. Ident. No.
Class II, Division 1 and 2 with Globe or
with Globe and Reflector
UL/NEC Temp. Ident. No.
Lamp
Type
Lamp
Watts
Supply
Wire
°C (°F)
Ambient
Temp
°C (°F)
Nameplate
Marking
Groups
Nameplate
Marking
Groups
PLT
(4-pin)
26 75 (167) 40 (104) T6
B,C,D
T4A E, F, G
PLT
(4-pin)
32 75 (167) 40 (104) T6
B,C,D
T4A E, F, G
PLT
(4-pin)
42 75 (167) 40 (104) T6
B,C,D
T4A E, F, G
PLT
(4-pin)
52
(2 x 26)
75 (167) 40 (104) T6 C, D T4 E, F, G
75 (167) 55 (131) T5 C, D
75 (167) 65 (149) T5 C, D
PLT
(4-pin)
64
(2 x 32)
75 (167) 40 (104) T6 C, D T4 E, F, G
75 (167) 55 (131) T5 C, D
75 (167) 65 (149) T5 C, D
PLT
(4-pin)
84
(2 x 42)
75 (167) 40 (104) T6 C, D T4 E, F, G
75 (167) 55 (131) T5 C, D
75 (167) 65 (149) T5 C, D
Catalog Numbering Guide
CJ F P 26 75 G BU L
Series:
CJ - Code•Master
Jr.
C - Code•Master 2
Mouning:
P - Pendant
C - Ceiling
B - Bracket
S - Stanchion
PB - Group B Pendant
SB - Group B Stanchion
Hub Size:
75 - 3/4”
10 - 1”
150 - 1-1/2” or 1-1/4”
Voltage:
BU - 120-277 V 50/60 Hz
A5 - 347 V 60 Hz
Lamp Type:
F - Fluorescent
Wattage:
26 - 26 Watts
32 - 32 Watts
42 - 42 Watts
52 - 52 Watts
64 - 64 Watts
84 - 84 Watts
Guard:
G - Guard provided
Blank - Guard not provided
Options:
L - Lamps Provided
F - Fused
Z - Zone 1
Exd IIB + H
2
Code•Master
PLT Factory Sealed Luminaires
Explosionproof, Dust-Ignitionproof
Integrally Ballasted. 26 W, 32 W, 42 W, 52 W, 64 W, 84 W Compact Fluorescent. For use with Threaded Metal Conduit.
NEC:
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4X
Suitable for use in wet locations
CEC:
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
CSA 4X
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© May 2019
497