Technical Bulletin
Applications
• Prevent passage of gases, vapors or ames from one portion of
conduit system to another. Restrict any explosion to the sealed
off enclosure. Prevent pressure piling within conduit system.
• Required in Class I, Division 1 and 2 locations within 18” of
enclosures containing apparatus that may cause arcs, sparks or
high temperatures.
• Required in Class I, Division 1 and 2 locations where 2” or larger
conduit enters enclosure, tting housing terminals, splices or
taps.
• Required in Class I, Division 1 and 2 locations at the boundary
where conduit leaves classied location.
• Required in Class I, Division 1 and 2 locations where two or
more enclosures are connected by 36” or less conduit. Seal
must be located within 18” of either enclosure.
• Required where cables (which exceed rate of gas or vapor
transmission permitted for seals) are used in Class I, Division 2
locations.
Features
• Explosionproof, dust-ignitionproof, raintight.
• Smooth, rounded integral bushing in each hub protects
conductor insulation.
• Accurately tapped, tapered threads for tight, rigid joints and
ground continuity.
• Removable nipple in male sealing tting may be used
interchangeably in top or bottom hub.
• EYS—for sealing vertical conduit. Large opening for damming
and lling.
• Expanded ll EYSEF/EYDEF— allow up to 40% conduit ll in
compliance with the National Electrical Code.
• EYSF/EYSM—for sealing vertical conduit. Large opening for
damming and lling.
• ESUF/ESUM— for sealing vertical or horizontal conduit. Pouring
spout rotates 90°. Removable cover provides full access for
damming 1/2” thru 1” sizes have threaded cover openings for
damming.
• EYF/EYM—close radius type for sealing vertical or horizontal
conduit runs.
• EYDM Drain Sealing Fittings—close radius type for sealing
vertical conduit runs. Access cover has drain valve for
automatic draining of water accumulation above the seal.
• UL Listed for use with Kwiko
™
A Sealing Compound. Also listed
with certain competitors sealing cement, contact factory for
details.
Standard Materials
• EYSF/EYSM, EYF/EYM and EYDM seals: malleable iron or
copperfree Almag 35 aluminum
• EYS, EYSEF/EYDEF, and ESUF/ESUM seals: malleable iron
• EYD and EYS seals: Grayloy
®
-iron
Standard Finishes
• Malleable iron and Grayloy
®
-iron products have triple-coat —
(1) zinc electroplate, (2) chromate, and (3) epoxy powder coat,
• Almag 35 aluminum products have epoxy powder coat
NEC/CEC Certifications and Compliances
• UL Standard: 886 (1203)
• UL Listed: E10444, E-34997
• CSA Standard: C22.2 No. 30
• CSA Certied: 065181
Related Products
• Kwiko
™
A sealing cement and ber ller
Illustrated Features
Sealing fittings prevent passage of gases, vapors or flames from
one portion of a conduit system to another. They also restrict
large amounts of ignitable gases or vapors from accumulating to
confine explosive pressure.
Appleton sealing fittings are suitable for Class I and II locations.
EYS, EYSF and EYD are for sealing vertical conduit. EY and ESU
are for sealing vertical and horizontal conduit. EYDM and EYD
also have drain valves.
Sealing Fittings
Explosionproof, Dust-Ignitionproof
UNILETS
™
for Use with Threaded Rigid Metal Conduit and IMC.
HAZARDOUS LOCATION FITTINGS: NEC/CEC EXPLOSIONPROOF SEALING FITTINGS
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© July 2020
676