Cut Sheet
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx nA nR IIC (Z2)
Class I, Zone 2, Ex nR IIC (Z) V
Class I, Zone 2, AEx nR IIC (ZB)
Class II, Division 1 and 2, Groups E, F, G
Class III
Simultaneous Exposure (Class I, Division 2/
Class II, Division 1)
Fixtures Outside Type (Salt Water)
Type 4X
IP66
C.W.A. – Constant Wattage Autotransformer. HX-HPF – High Reactance High Power Factor Autotransformer. Super C.W.A. – Super Constant Wattage Autotransformer.
➋ 150 W HPS units equipped with ballasts to operate 55 volt lamps only.
V CSA Certification only.
Electrical Specifications
Line
Voltage
Type of
Ballast
Starting
Amps
Operating
Amps
Total
Watts
50 Watt High Pressure Sodium
120 HX-HPF 0.58 0.58 64
208 HX-HPF 0.35 0.33 64
240 HX-HPF 0.31 0.29 64
277 HX-HPF 0.25 0.25 64
347
V
HX-HPF 0.26 0.21 68
70 Watt High Pressure Sodium
120 HX-HPF 0.90 0.82 94
208 HX-HPF 0.50 0.48 94
240 HX-HPF 0.44 0.41 94
277 HX-HPF 0.35 0.36 94
347
V
HX-HPF 0.30 0.30 94
480 HX-HPF 0.21 0.21 94
100 Watt High Pressure Sodium
120 HX-HPF 1.30 1.15 130
208 HX-HPF 0.76 0.67 130
240 HX-HPF 0.66 0.60 130
277 HX-HPF 0.60 0.52 130
347
V
HX-HPF 0.45 0.39 130
480 HX-HPF 0.33 0.31 135
480 C.W.I. 0.17 0.30 130
600 C.W.I. 0.14 0.24 130
150 Watt High Pressure Sodium ➋
120 HX-HPF 2.00 1.70 188
208 HX-HPF 1.15 0.95 188
240 HX-HPF 1.00 0.85 188
277 HX-HPF 0.85 0.72 188
347
V
HX-HPF 0.52 0.56 188
480 HX-HPF 0.50 0.47 189
480 C.W.I. 0.25 0.42 190
600 C.W.I. 0.19 0.35 190
70 Watt Pulse Start Metal Halide
120 HX-HPF 0.80 0.85 95
208 HX-HPF 0.50 0.52 95
240 HX-HPF 0.43 0.44 95
277 HX-HPF 0.39 0.39 95
347
V
HX-HPF 0.20 0.28 88
480 HX-HPF 0.26 0.23 95
100 Watt Pulse Start Metal Halide
120 HX-HPF 1.20 1.15 130
208 HX-HPF 0.70 0.70 130
240 HX-HPF 0.61 0.58 130
277 HX-HPF 0.55 0.50 130
347
V
HX-HPF 0.40 0.40 129
480 HX-HPF 0.30 0.35 140
Line
Voltage
Type of
Ballast
Starting
Amps
Operating
Amps
Total
Watts
150 Watt Pulse Start Metal Halide
120 HX-HPF 1.75 1.60 188
208 HX-HPF 1.30 1.00 188
240 HX-HPF 0.85 0.80 188
277 HX-HPF 0.77 0.70 188
347
V
SuperC.W.A. 0.65 0.55 185
480 SuperC.W.A. 0.45 0.42 185
175 Watt Pulse Start Metal Halide
120 SuperC.W.A. 0.90 1.78 199
208 SuperC.W.A. 0.50 1.08 199
240 SuperC.W.A. 0.35 0.89 199
277 SuperC.W.A. 0.30 0.76 199
347
V
SuperC.W.A. 0.25 0.65 208
480 SuperC.W.A. 0.25 0.50 213
175 Watt Metal Halide
V
120 C.W.A. 1.30 1.80 210
208 C.W.A. 0.75 1.04 210
240 C.W.A. 0.65 0.90 210
277 C.W.A. 0.55 0.80 210
347 C.W.A. 0.50 0.65 210
480 C.W.I. 0.20 0.45 215
600 C.W.I. 0.16 0.37 215
175 Watt Metal Halide V
120 SuperC.W.A. 1.30 1.80 213
208 SuperC.W.A. 0.75 1.10 213
240 SuperC.W.A. 0.65 0.90 213
277 SuperC.W.A. 0.55 0.80 213
480 SuperC.W.A. 0.35 0.45 213
250 Watt Metal Halide V
120 SuperC.W.A. 1.20 2.60 298
208 SuperC.W.A. 0.65 1.50 298
240 SuperC.W.A. 0.60 1.30 298
277 SuperC.W.A. 0.50 1.12 298
480 SuperC.W.A. 0.30 0.65 298
Lighting
Lighting: EncLosEd and gaskEtEd — arEa — hid
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
964
Mercmaster
™
III HID 50-250 Watt Luminaire Electrical Specifications
High Pressure Sodium and Pulse Start Metal Halide
Listed for simultaneous exposure to combustible dusts and flammable gases or vapors.