NEMA 4X
PCD2 Series Factory Sealed Hazardous Location Photocontrol
For Use in Class I, Division 2, Groups A, B, C, D Locations
Maintains Class I, Division 2 rating for Mercmaster III, Mercmaster III Low Profile, Mercmaster III 50-250 and 400 Series Luminaires; Mercmaster LED Series.
Applications
• Encapsulatedphotocontrolprovidesautomaticdusk-to-dawn
lightingcontrolinClassI,Division2locations.
• Typicalapplicationsincludewalkways,securityareasandany
otheroutdoorlightingapplication.
• ForusewithallMercmasterLEDseries.
• ForremotemountinginFSBoxes.
Features
• Factorysealeddesigneliminatestheneedforanexplosionproof
enclosure.
• One-piecemoldedGEUltem1000translucentlensassembly,
UL94V-0compliant.
• Canbeeasilyinstalledintheeld.
• Solidstatedesignforperformanceandreliability.
• Availablefor120,208,240,or277volts.
• 1000V.A.Voltage/Ampere
• Minimumtimedelay:15secondstoeliminatenuisiancetripping.
• Providedwith(3)18AWGstrandedleads152.4mm(6.00in)
length.
• Willtthroughstandard1/2”knockout.
• Suppliedwithlocknutandgasket.
Materials
• Encapsulatedwithepoxysealingcompound
• FSCover:aluminum
NEC/CEC Certifications and Compliances
• ULStandard:1604–Hazardous(Classied)Locations
• cULusRecognized
Voltage Range Max VA
Max Current
Amps
Suffix Designation
Catalog Number
Factory Installed Photocontrol — Not for ceiling or pendant cone
Add to fixture catalog after voltage; i.e.: MLLEDA32P5BU1.
Mercmaster III wall mounting hood with
photocontrol installed shown
120V,50/60Hz 1000 8.3Amp 1
208V,50/60Hz 1000 4.8Amp 2
240V,50/60Hz 1000 4.2Amp 3
277V,50/60Hz 1000 3.6Amp 4
Photocontrol for Field Installation
120V,50/60Hz 1000 8.3Amp PC120D2
208V,50/60Hz 1000 4.8Amp
PC247D2240V,50/60Hz 1000 4.2Amp
277V,50/60Hz 1000 3.6Amp
Photocontrol in FS Cover for Use with FS/FD Box
Supplied with two stainless steel screws. For neoprene gasket, order catalog number FS-GKR-1N.
120V,50/60Hz 1000 8.3Amp FSKA-PC120D2
208V,50/60Hz 1000 4.8Amp
FSKA-PC247D2
240V,50/60Hz 1000 4.2Amp
277V,50/60Hz 1000 3.6Amp
17.5 mm
(0.69”)
28.7 mm (1.13”)
34.9 mm
(1.38”)
65.0 mm (2.56”)
30.2 mm (1.19”)
49.2 mm (1.94”)
17.5 mm
(0.69”)
28.7 mm (1.13”)
34.9 mm
(1.38”)
65.0 mm (2.56”)
30.2 mm (1.19”)
49.2 mm (1.94”)
17.5 mm
(0.69”)
28.7 mm (1.13”)
34.9 mm
(1.38”)
65.0 mm (2.56”)
30.2 mm (1.19”)
49.2 mm (1.94”)
Fixtures with photocontrols are not rated IP66, Type 4X, marine outside type (salt water), or Class II.