Cut Sheet
Lighting — LED
NEC/CEC ENClosEd aNd GaskEtEd — arEa
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© January 2016
1374
Technical Data
Lamp
Ambient
Temperature
°C (°F)
Supply Wire
Temperature
°C (°F)
NEC/CEC
Gas Dust Gas/Dust
Model Type
Class I,
Division 2 Groups Class I, Zone 2,
Class II,
Division 1
and 2 Groups
Simultaneous
Class I, Division 2/
Class II, Division 1
MLLED2
NEMA
TypeV
LED
40(104) 60(140) T4
A,B,C,D
T4 T6
E,F,G
T4
55(131) 75(167) T4 T4 T6 T4
MLLED3
NEMA
TypeV
LED
40(104) 60(140) T4
A,B,C,D
T4 T6
E,F,G
T4
55(131) 75(167) T4 T4 T6 T4
MLLED4
NEMA
TypeV
LED
40(104) 60(140) T4
A,B,C,D
T4 T6
E,F,G
T4
55(131) 75(167) T4 T4 T6 T4
“T” Numbers Represent the Maximum Internal Temperature or Maximum Surface Temperature
NEC/CEC
“T” # T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
Temp.
Range
ºC (˚ºF)
351-
450
326-
350
301-
325
281-
300
261-
280
231-
260
216-
230
201-
215
181-
200
166-
180
161-
165
136-
160
121-
135
101-
120
86-
100
85
(664-
842)
(619-
662)
(574-
617)
(538-
572)
(502-
536)
(448-
500)
(421-
446)
(394-
419)
(358-
392)
(331-
356)
(322-
329)
(277-
320)
(250-
275)
(214-
248)
(187-
212)
(185)
NEC/CEC:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEC/CEC:
Type 3R, 4, 4X
IP66
Simultaneous Exposure
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
Mercmaster™ LED Low Profile Luminaires
Enclosed and Gasketed Fixtures
Lamp Comparison Chart
Model
Line Current
Amps
Input
Power
Power
Factor THD
Lumens
CRI
Lamp
Life
(Hours)
Color
Temp
CCT
Equivalent
HID
Luminaire
Polycarbonate
Clear Globe
Polycarbonate
Diffused
Globe
Glass
Clear
Globe
Type V
Prismatic
Glass Refractor
NEMA Type V
MLLED2
.21@120V 26
>.97 <20% 2400 2300 2500 2200 >70 60,000+ 5700K 70W
.10@277V 26
MLLED3
.29@120V 35
>.97 <20% 3400 3300 3600 3100 >70 60,000+ 5700K 100W
.13@277V 34
MLLED4
.41@120V 48
>.88 <20% 4800 4600 5000 4300 >70 60,000+ 5700K 150W
.20@277V 48
Surge Protection Common/Differential Mode:
100kHz Ring Wave (w/t 30Ω): 6 KV
1.2/50 µs Combination Wave (w/t 2Ω): MLLED2,
MLLED3 4 KV; MLLED4 3 KV
Clear and diffused polycarbonate globes are not rated for Class II, Division I environments
T numbers represent the maximum internal temperature for Class I, Division 2 and Class I, Zone 2 locations designated by the NEC.
T numbers represent the maximum surface temperature under a dust blanket for Class II, Division 1 as designated by the NEC.
All lumen values are typical (tolerance +/- 10%).
Certification pending for Glass Globe.