SYMPTOM
Humidifier or Humidifier Control “chatters” or clicks On and
Off rapidly
TROUBLESHOOTING PROCEDURE
Check for steady 22 VAC to 30 VAC across the “R” and “C”
terminals of the Humidifier Control with a voltmeter.
Check, with a voltmeter, that the HVAC signal across the
“W/G” and “Cf terminals of the Humidifier Control is a
steady 22 VAC to 30 VAC.
Make sure that the Outdoor Temperature Sensor wiring is
not running alongside other wires carrying high voltage
(120 VAC or higher). (Automatic Mode Only)