Install Instructions

TROUBLESHOOTING
DISPLAY IS BLANK
If Power LED is not illuminated at the 6000 Series Hub check the following:
Check circuit breaker and reset if necessary.
Make sure power switch at heating & cooling system is on.
Make sure furnace door is closed securely.
HEATING SYSTEM DOES NOT RESPOND (“HEATING” APPEARS ON SCREEN)
Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.
Check for 24VAC between the heat terminal (W) and the transformer common. If 24VAC is present, the 6000 Series Zone Control System is
functional. Check the heating equipment to find the cause of the problem.
Check for loose or broken wires between the 6000 Series Hub and the heating equipment.
COOLING SYSTEM DOES NOT RESPOND (“COOLING” APPEARS ON SCREEN)
Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem
Check for 24VAC between the cooling terminal (Y) and the transformer common. If 24VAC is present, the 6000 Series Hub is functional. Check the
cooling system to find the cause of the problem.
Check for loose or broken wires between the 6000 Series Hub and the cooling equipment.
FAN DOES NOT TURN ON IN A CALL FOR HEAT
Check Installer Setting Fan Control In Heating / Heat Pump Auxiliary Type, to make sure the fan control is properly set to match the type of system.
27