Goliath Drain Pan Installation Instructions

Rev. 10/08
AG-4100
AG-4200
AG-4300
Installation Instructions:
Titan, Spartan, Goliath and Goliath Furnace Series
Secondary Condensate Pans & 4000 Series Switches
Work Safe, READ THIS!
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS AND INSTRUCTIONS PRIOR TO STARTING INSTALLATION MAY
CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
STOP/READ: This device must be installed in accordance with manufacturer’s instructions. This unit must be in accordance with all applicable local plumbing, drainage and
electrical codes.
WARNING: Remove electrical shock hazard – DISCONNECT THE POWER BEFORE INSTALLATION to avoid electrical shock and/or equipment damage. Do not use
on circuits exceeding 24 volts to avoid damage to switch, shock or fire hazard.
CAUTION: In some situations the switch may cause the unit to rapidly cycle on and off as water level rises slowly in pan. After a brief period the unit will turn off completely.
Condensation drain must be serviced if this occurs.
CAUTION: In any installation where property damage and/or personal injury might result from an inoperative switch due to power outages, a back-up system(s) and or alarm
should be installed.
NOTICE: The AquaGuard Drain pans and float switches must only be installed by a licensed contractor or under the direct supervision of same. Condensation pan must be
properly maintained after installation and be kept free from foreign objects, rust or other obstructions that might interfere with the proper operation of the AquaGuard float
switch.
TITAN DRAIN PAN INSTALLATION:
(To ensure proper performance of product, instructions must be followed.)
1. Inspect the drain pan for any shipping damage that may have occurred. If cracked or broken, DO NOT USE.
2. Make sure drain pan is a minimum of 3” greater (1.5” clearance per side) in length and width than the equipment dimension.
3. Make sure the pan-mounting surface is level and free of any debris.
4. For solid surface applications, place HVAC unit on blocks or 2-4x4 boards running the full length of the Titan pan between the HVAC unit and the Titan pan between
the HVAC unit and the pan on either of the water displacement ridge. (fig. 1)
5. For hanging application, place 2-4x4 boards running the full length of the Titan pan between the HVAC unit and the pan on either side of the water displacement
ridge. (fig. 2). Pressure treated wood will not damage the pan.
6. Approved steel supports are to be placed 6” to 8” from the end of the 4x4 as shown. (fig. 3).
IMPORTANT! When brazing, take precautions to prevent pan from coming in contact with torch heat or brazing materials. It’s recommended that a damp cloth be
placed under the lines being brazed.
(fig. 1) (fig. 2) (fig. 3)
HORIZONTAL INSTALLATION OF SPARTAN, GOLIATH, AND GOLIATH FURNACE DRAIN PAN:
(To ensure proper performance of product, instructions must be followed.)
1. Refer to Furnace/Air Handler instructions prior to installation.
2. Inspect the drain pan for any shipping damage that may have occurred. If cracked or broken, DO NOT USE.
3. Make sure drain pan is a minimum of 3” greater (1.5” clearance per side) in length and width than the equipment dimension.
4. Make sure the pan-mounting surface is level and free of any debris.
IMPORTANT! When brazing, take precautions to prevent pan from coming in contact with torch heat or brazing materials. It’s recommended that a
damp cloth be placed under the lines being brazed.
5. Insert rubber Vibration Isolators (Spartan, Goliath and Goliath Furnace series only) in the most appropriate support receptacles. (fig.4) It is not necessary to fill every
receptacle.
6. For non-furnace applications, position air handler in the center of the pan. (fig. 5)
7. For furnace installations, refer to manufacturer’s instructions regarding clearance specifications. Optional AG-MJ1 Riser Kit may be used to achieve additional
1” clearance between furnace and pan.
8. For furnace installations, position the furnace with the heavy side of the unit resting on “back side” of the pan, i.e. the side directly opposite of the float switch. (fig.
4)
Caution: AquaGuard SPARTAN and GOLIATH FURNACE SERIES Drain Pans are not designed for hanging applications.